Viessmann Boiler: Diagnosis and service scans (brief scan lines 1 to 8)
Diagnosis and service scans (brief scan lines 1 to 8) on a Viessmann boiler: The control unit can scan a set of values in numbered lines. Which values appear depends on the installed system. Lines 1 to 8 cover system type, software and appliance version, burner control unit, flow rate sensor, and LON addressing. Line 9 covers remote control type, line 10 covers pump type, and line 11 covers mixing valve extensions. The manual's scan table is partly jumbled in this extract, so check the full table on the original page.
Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125
How to fix diagnosis and service scans (brief scan lines 1 to 8): step by step
- Use the diagnosis scan on the control unit to read the values.
- Line 1: system type (01 to 10), control unit software version, programming unit software version.
- Line 2: appliance version and device identification.
- Line 4: burner control unit type and version.
- Line 6: flow rate sensor switching state (flow rate too low or not present).
- Line 9: remote control type (0 none, 1 Vitotrol 200 series, 2 Vitotrol 300 series or Vitohome) and its software version for each heating circuit.
- Line 10: internal and external pump type (0 none, 1 Wilo, 2 Grundfos) and variable speed pump status.
- Line 11: mixing valve extension present for heating circuits M2 and M3.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
More service & test modes tips for boiler
Source: Vitodens 200-W B2HB service instructions, p. 72-73. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.