Updated · by Aurora Star Tech Inc.

DHW supply and return piping size on a Viessmann boiler: Pipe between the boiler DHW connections and the Viessmann DHW tank must be at least 1¼ in. This lets the field pump's residual head overcome the DHW coil resistance and still feed the boiler heat exchanger. With a non-Viessmann tank, also calculate the coil pressure drop against the pump's residual head. Undersized piping can cause short-cycling and poor DHW supply.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB

How to fix dhw supply and return piping size: step by step

  1. Use at least 1¼ in. pipe between boiler DHW connections and the DHW tank.
  2. With a non-Viessmann tank, calculate coil pressure drop versus the field pump's residual head.
  3. Confirm enough flow reaches the boiler heat exchanger.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

More other tips for boiler

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.