Other: Boiler tips (part 13 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

DHW frost protection

Viessmann · DHW tank

If domestic hot water temperature drops below 50 F / 10 C, the tank is heated to 68 F / 20 C.

DHW hygiene function (B1HE only)

Viessmann · B1HE

Heats DHW to a higher target temperature for one hour. Activate it through the operating instructions.

  1. Activate the hygiene function as described in the operating instructions.

DHW hygiene function settings

Viessmann · Vitocrossal 200 CI2 DHW tank heating

The hygiene function heats the DHW to a higher target for 1 hour. If the final temperature is not reached, the DHW heating can be aborted after the set time. Set the abort time to 60 minutes while hygiene runs (factory is 240 minutes).

  1. Configure the hygiene function via the HMI or ViGuide Web Pro (parameters 874.0 to 876.0).
  2. For the hygiene run, set parameter 1087.0 to 60 min so heating aborts early if the final temperature is missed.

DHW priority and heating circuit pump behaviour

Viessmann · Heating circuits with DHW tank

With DHW priority (coding A2: 2), the set supply temperature drops to 0 °C (32 °F) while the DHW tank heats, the mixing valve closes and heating circuit pumps stop. Without priority, the heating circuit keeps its set value.

  1. Check coding A2 to confirm whether DHW priority is set.
  2. If the heating circuit must keep running during DHW heating, do not select priority control.

DHW recirculation line insulation

Viessmann · Vitodens 200-W B2HB with DHW recirculation

Recirculation lines lose a lot of heat if poorly insulated. Viessmann recommends effective insulation on DHW recirculation lines that are 23 ft (7 m) or longer.

  1. Insulate DHW recirculation lines that are 23 ft (7 m) or longer.
  2. Check the recirculation pump and line layout against the Vitocell tank layout on this page.

DHW recirculation pump brief operation

Viessmann · DHW recirculation pump on EA1 input

The DHW recirculation pump starts briefly when a pushbutton closes the contact at DE1, DE2 or DE3. The runtime is set at coding address 3D.

  1. Assign the input to brief recirculation operation (DE1, DE2 or DE3).
  2. Set the runtime at coding address 3D in the General group.

DHW recirculation pump brief operation via EA1 input

Viessmann · DHW recirculation pump, output aBJ

A pushbutton on DE1, DE2 or DE3 can start the DHW recirculation pump outside its time program. Run time is set by coding 3d in the General group. Output aBJ can signal a central fault or reduced mode (reduces heating circuit pump speed); its function is set by coding 5c in the General group.

  1. Wire a pushbutton to DE1, DE2 or DE3 and set the matching input function code.
  2. Set run time at coding 3d (General group).
  3. Set output aBJ function at coding 5c (General group).

DHW recirculation pump use

Viessmann · Vitocrossal 300 CU3A

Run the DHW recirculation pump only when hot water is regularly drawn off, using a time program.

  1. Set the DHW recirculation pump time program to match regular draw-off periods.

DHW safety valve check

Viessmann · DHW tank safety valve

The DHW tank safety valve must be checked every six months by venting it. The valve seat can become contaminated, and water may drip during heat-up. The outlet must stay open to atmosphere.

  1. Vent the DHW tank safety valve every six months, following the valve manufacturer's instructions.
  2. Do not close off the valve outlet.

DHW supply and return piping size

Viessmann · Vitodens 200-W B2HB

Pipe between the boiler DHW connections and the Viessmann DHW tank must be at least 1¼ in. This lets the field pump's residual head overcome the DHW coil resistance and still feed the boiler heat exchanger. With a non-Viessmann tank, also calculate the coil pressure drop against the pump's residual head. Undersized piping can cause short-cycling and poor DHW supply.

  1. Use at least 1¼ in. pipe between boiler DHW connections and the DHW tank.
  2. With a non-Viessmann tank, calculate coil pressure drop versus the field pump's residual head.
  3. Confirm enough flow reaches the boiler heat exchanger.

DHW tank and safety valve maintenance

Viessmann · Vitocrossal 300 CA3B

DHW tank must be cleaned no later than 2 years after commissioning and as needed after that. The DHW tank safety valve must be checked every six months.

  1. Have a qualified heating contractor clean the inside of the DHW tank and DHW connections.
  2. Check the DHW tank safety valve every six months by venting it.
  3. Make sure the valve outlet is open to the atmosphere and not closed off.

DHW tank maintenance

Viessmann · Vitocrossal 300 CA3B DHW tank

The DHW tank must be cleaned and serviced no later than 2 years after commissioning and as needed after that. Only a qualified heating contractor should clean inside the tank and DHW connections.

  1. Clean and service the DHW tank within 2 years of commissioning, then as needed.
  2. Refill any water treatment equipment in the cold supply in good time, following its manufacturer's instructions.

DHW tank sensor and tempering valve with non-Viessmann tanks

Viessmann · Vitocrossal 200 CI2 399 to 2000

If a DHW tank other than the Viessmann Vitocell 300 is used, confirm the Viessmann DHW tank temperature sensor works correctly with the tank manufacturer. A temperature tempering valve is strongly recommended in the DHW supply line. For DHW tank applications, calculate the coil pressure drop against the field-supplied DHW pump residual head to make sure enough water flows through the boiler heat exchanger. Insufficient flow can cause short-cycling and poor DHW supply.

  1. Verify the Viessmann DHW sensor with the tank manufacturer if the tank is not a Vitocell 300.
  2. Install a temperature tempering valve in the DHW supply line.
  3. Calculate tank coil pressure drop against the DHW pump residual head.
  4. Confirm enough flow reaches the boiler heat exchanger.

DHW tank sensor check and tempering valve

Viessmann · Vitodens 200-W B2HA 45, 60 with DHW storage tank

A non-Viessmann DHW tank requires the Viessmann DHW tank sensor to be verified with the tank manufacturer. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. For a non-Viessmann tank, verify the Viessmann DHW tank temperature sensor operation with the tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

DHW tank with temperature switch (Aquastat)

Viessmann · Vitodens 100-W B1HE/B1KE with Aquastat DHW tank

Some DHW menu items (On/Off, time program, hygiene program, recirculation pump, temperatures and scald protection) do not apply to systems that use a DHW tank with a temperature switch such as an Aquastat.

  1. Confirm whether the system has a DHW tank with an Aquastat before looking for these DHW menu items.

DHW temperature shows 'Without function'

Viessmann · Vitotronic 200-H with central DHW tank

When DHW is supplied by a central DHW tank, the control cannot set the DHW temperature and shows 'Without function'.

Diagnosis display items and brief scan lines

Viessmann · Vitodens 200-W B2HB diagnosis

Diagnosis shows outdoor temperature adjustment and actual, boiler setpoint and actual, DHW setpoint and actual, supply setpoint and actual, common supply setpoint and actual, boiler coding card, and brief scan pages 1 to 8. Slope A1 and shift A1 apply to a heating circuit with mixing valve; Slope M2 and shift M2 apply to a second mixing valve circuit. Low-loss header values apply to a low-loss header. Brief scan lines cover system type, software versions, KM BUS participants, burner control unit type and version, flow rate sensor state, and LON addresses and software.

  1. Press D in the outdoor temperature display to reset adjusted outdoor temperature to actual.

Diagnosis scan values

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Diagnosis scan shows slope A1 and shift A1, slope M2 and shift M2, outdoor temperature adjustment and actual, boiler setpoint and actual, DHW setpoint and actual, supply temperature setpoint and actual, common supply setpoint and actual, boiler coding card, and brief scans 1 to 8. The manual's explanation column for these lines is jumbled in this text, so match each item to the manual page before relying on it.

Differential pressure bypass valve

Viessmann · Vitotron 100 VLN2

The built-in bypass valve keeps a minimum flow through the boiler and reduces noise when zone valves are used.

  1. Do not remove or block the bypass valve when setting up the system.

Digital room controller overrides heating program

Viessmann · Systems with a digital room controller

If a digital room controller with a heating program input is connected, its own heating program replaces the matching program on this controller.

Digital time switch and control functions

Viessmann · Vitotronic 200 HO1B

The digital time switch has a 7-day program, automatic daylight savings change, up to four switching periods per day, a 10 minute minimum switching interval and 14 day power backup. Zone circuits support up to three zones using setpoint or outdoor reset.

  1. Set daily switching times for heating, DHW and the DHW recirculation pump as needed.
  2. Use the start-up wizard to set up zone circuits.
  3. Choose setpoint or outdoor reset operation for each zone circuit.

Direct vent exhaust pressure and sealing

Viessmann · Direct vent systems

Direct vent exhaust runs under positive pressure from the burner, so every joint must be airtight.

  1. Tighten all vent connection and observation port screws.
  2. Use high temperature silicone sealant where needed.
  3. Do not alter vent components except cutting the flex pipe to length.

Direct vent is limited to some sizes

Viessmann · VR1 22, 27, 33, 91, 105, 140

Direct vent is only offered for VR1 22, 27, 33, 91, 105 and 140. Direct vent burners are not available for the larger sizes. Follow the separate direct vent installation supplement for those installs.

Direct vent operation in contaminated-air rooms

Viessmann · Vitocrossal 200 CI2 399 to 2000

Where halogenated hydrocarbons from sprays, paints, solvents or cleaning agents are expected in the room air, the boiler must run in direct vent (sealed combustion) operation only.

  1. Check the room for halogenated hydrocarbon sources before installation.
  2. If contamination is expected, set up the boiler for direct vent (sealed combustion) operation only.

Discharge static before touching electronics

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

Electronic modules can be damaged by electrostatic discharge.

  1. Touch a grounded object, such as a heating or water pipe, before working on the control modules.

Discoloured heat exchanger is normal

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

Discolouration of the stainless steel heat exchanger surface is a normal result of combustion. It does not affect function or service life, so do not treat it as a fault.

Disconnect power and label wires before servicing

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Power must be off before any boiler service. Wiring errors can cause dangerous operation, so verify correct operation after servicing. Replace any original wire only with an exact equivalent.

  1. Disconnect power before servicing the boiler.
  2. Label all wires before disconnecting them.
  3. Replace any damaged original wire only with an exact equivalent.
  4. Assign only one function or accessory to each connection.
  5. Verify correct operation after any control service.

Disconnect power before any wiring

Viessmann · All Vitotronic 300 GW2 wiring

Every connection on these pages starts with isolating the power to the burner and the control.

  1. Disconnect power to the burner and boiler control before making any connection.
  2. Confirm the power is off before removing plugs or jumpers.

Disconnect power before any wiring work

Viessmann · All Versatronik 10.WB1 wiring

Before any work, disconnect the boiler and the Versatronik from the 120 VAC supply. Check all wiring before applying power. The boiler pump output to the Versatronik must not be live. Skipping this can cause early failure of the pump module.

  1. Disconnect the boiler and Versatronik from 120 VAC power.
  2. Check all wiring connections.
  3. Apply power only after the check, then test operation.

Disconnect power before servicing

Viessmann · Vitocrossal 300 CA3B boiler

Power inside the boiler junction box must be disconnected before any service work on the boiler.

  1. Disconnect power inside the boiler junction box before servicing the boiler.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.