Viessmann Boiler: CSD-1 field test of fixed high limit
CSD-1 field test of fixed high limit on a Viessmann boiler: Where required by law, test the fixed high limit by simulating an overheat. Viessmann is not responsible for damage caused by overheating during this test. A tripped fixed high limit needs a manual reset of the control.
Applies to: Vitocrossal 300 CU3A 26 to 199
How to fix csd-1 field test of fixed high limit: step by step
- Run the boiler to high fire using the relays test.
- Throttle the boiler valve until the burner runs with as little flow as possible.
- When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Let the boiler temperature keep rising until the fixed high limit trips.
- After the fixed high limit trips, slowly open the boiler valve to cool the boiler down.
- Reset the boiler control manually.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
More service & test modes tips for boiler
Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.