Viessmann Boiler: Corrosion protection for heating water
Corrosion protection for heating water on a Viessmann boiler: Oxygen in the heating water causes corrosion. Keep the system sealed and at positive pressure, and keep the pH in range.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
How to fix corrosion protection for heating water: step by step
- Keep the sealed system above atmospheric pressure at all points, including the pump suction side.
- Check the expansion vessel precharge at least during the annual service.
- Use a corrosion-resistant separation (heat exchanger) where gas-permeable plastic pipe is used, such as in underfloor heating.
- Where oxygen ingress is a risk, consider a sodium sulphite oxygen binder at 5 to 10 ppm.
- Keep the heating water pH between 8.2 and 9.5.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B service instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.