Other: Boiler tips (part 12 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Control keys and menu access
Viessmann · Vitotronic 200 HO1B user interface
The back key cancels a started setting or goes back one menu step. The cursor keys scroll the menu and change values. OK confirms a selection or saves a setting. The ? key has no function. Tapping the menu key opens settings and scanning, which includes Information, Further adjustments, Emissions test mode and Heating program.
- Tap the menu key to enter settings and scanning.
- Use the cursor keys to move through the menu and change values.
- Press OK to save, or the back key to cancel.
Control layout (Vitocontrol-S)
Viessmann · Vitocontrol-S, VD2/CT3/CM2
The Vitocontrol-S has heating circuit buttons, heating program buttons, a normal and reduced room temperature selector, party and energy saving buttons, a holiday program, time programs for central heating, DHW and DHW circulation, DHW temperature selector, heating curve shift and slope, a time/date setting, and a boiler sequence display. It also has green and red status lights and fuse F1.
- Use the status lights to confirm the operating state and any fault.
- Check the boiler sequence display for the current boiler state.
Control options and side-mounted control in North America
Viessmann · All VD2 models 320 to 1080
The boiler is designed for Vitotronic or Dekamatik digital boiler and heating system control. In North America only the side-mounted control option is offered, so use the side-mounted control dimensions when planning clearances.
- Confirm the control type (Vitotronic or Dekamatik) before commissioning.
- For North American installs, plan the room for the side-mounted control dimensions.
Control panel and display indicators
Viessmann · Vitodens 100-W WB1B control panel
The LCD shows boiler water temperature in °F or a fault code. Other indicators: heating pump output on when the room thermostat is closed; DHW pump output on when DHW call is closed; burner firing rate; burner in operation; fault; service mode; comfort function started or stopped. Selector dials set DHW temperature and boiler water temperature. An ON/OFF switch and gas shut-off valve are also on the panel. The pressure gauge is on the control panel.
- Lift the flap and pull the control unit cover down to reach the boiler controls.
Control panel elements
Viessmann · Vitotronic 200 control panel
Lettered controls on the panel include heating circuit selection, reduced, standard and DHW temperature, standby, DHW only, heating and DHW, economy and party modes, information, basic settings, acknowledgment, value adjustment, time programs, holiday program, time/date, and heating curve level and slope.
Control PCB and display overview
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Board list and display indicators on the extension PCB for heating circuits 2 and 3.
- V1 red fault display: indicates a fault.
- V2 green operating mode display: indicates operating mode.
- S3 emissions test switch is on the extension PCB.
- A9 coding card and A7 Optolink PCB / emissions test switch are on the control board set.
Control unit display symbols
Viessmann · Vitodens 200-W B2HB control unit
Symbols shown on the display depending on system version and operating state.
- HC1 (2, 3): heating circuit selected in the standard menu.
- Frost protection monitoring active.
- Central heating with standard temperature.
- Central heating with reduced temperature.
- Party mode and Economy mode enabled.
- Solar circuit pump running (with solar thermal system).
- Burner in operation.
- Service message and Fault message indicators.
Control unit features and external connections
Viessmann · Vitodens 100-W B1HE and B1KE
The integrated control has an LCD display, push-button setting of boiler water temperature, adjustable high limit, burner fault display and reset, a pressure gauge, a fuse, and integrated WiFi. It can take a room thermostat or external control, an external heat demand, a DHW temperature sensor, a Viessmann outdoor sensor (field wired), and instantaneous DHW control on B1KE.
Control unit layout (Vitotronic 100, GC1)
Viessmann · Vitotronic 100, GC1 on each boiler
The Vitotronic 100, GC1 has a manual override, value selector buttons, information and confirmation buttons, a factory settings button, a display window, an adjustable high limit, a manual reset fixed high limit, a power on/off switch, fuses F1 and F2, and green and red status indicators. The green light shows operating status and the red light shows a fault.
- Use the green indicator to confirm operating status.
- If the red fault indicator is on, look up the fault in the troubleshooting section of the manual.
Control unit modules and programming unit functions
Viessmann · Vitotronic 300-K MW1S control panel
Component overview from the parts list. Module A1 is the power supply, A2 the cascade electronics, A3 the power module, and the front panel has heating circuit selector keys.
- Power supply module A1: fuse F1, see the fuse data on p. 120.
- Cascade electronics module A2: microprocessor with software; replace per the PCB procedure.
- Power module A3 and extension module: fit as listed in the parts list.
- Programming unit (in the control panel front door) sets heating program, set values, switching times, heating curve (slope and shift), date, time and economy/party mode.
- Displays temperatures, operating conditions and faults.
Control wiring safety and replacement rules
Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125 control wiring
Disconnect power before servicing the boiler. Label every wire before disconnecting it, since wiring errors can cause dangerous operation. Any original supplied wire that must be replaced needs an exact equivalent. Verify correct operation after any control service. Each connection point accepts only one function or accessory.
- Disconnect power before servicing the boiler.
- Label all wires before disconnecting them.
- Replace any original wire only with an exact equivalent.
- Assign only one function or accessory to each connection.
- Verify correct operation after servicing the controls.
Controls and display elements
Viessmann · Vitotronic 200-H user interface
Overview of the control keys and display symbols on the user interface: heating circuit selection keys, time programs, DHW and room temperature, heating curve slope and level, time/date, operating modes (standby, DHW only, heating and DHW), energy saving and party mode, and the adjust, confirm and information keys. A rotary selector sets the standard room temperature and a flap covers the controls.
- Select the heating circuit with its selection key before making adjustments.
- Use the adjust key to change values and the confirm key to save them.
Controls and indicators on the Vitotronic 100 GC1
Viessmann · Vitotronic 100 GC1 boiler control
Front panel items: override switch; boiler water temperature and domestic hot water temperature selectors (no function on multi-boiler systems); value selection buttons; information and confirmation buttons; basic setting; display window; heating program selector buttons (no function on multi-boiler systems); adjustable high limit; fixed high limit reset button; control on/off switch; fuses F1 and F2; TUV button; green operating status indicator; red fault indicator.
Convert fault codes from decimal to hex
Viessmann · Versatronik 581 gateway fault reporting to BMS
The gateway sends fault codes as decimal numbers in a SNVT_count variable. Viessmann displays them in hex, so convert before comparing with the code tables.
- Read the fault value from the gateway as a decimal number.
- Convert it to hexadecimal.
- Look up the hex value in the fault code tables (appendix A).
Convert gateway fault values from decimal to hex
Viessmann · Tridium/Niagara BMS integration with Versatronik 585
The gateway reports fault codes as decimal numbers. Convert them to hex to match the Viessmann code shown on the control. Some BMS software can do this with a mask or enum conversion object.
- Read the decimal fault value from the gateway.
- Convert it to hexadecimal.
- Match it to the hex code in the fault code table.
Copy a time program to other days
Viessmann · Time programs
Copies one day's time program to other selected days.
- Select the heating circuit and the source day.
- Select the target days.
- Confirm and exit.
Corrosion protection for heating water
Viessmann · Vitocrossal 300 CA3B 2.5 to 6.0
Oxygen in the heating water causes corrosion. Keep the system sealed and at positive pressure, and keep the pH in range.
- Keep the sealed system above atmospheric pressure at all points, including the pump suction side.
- Check the expansion vessel precharge at least during the annual service.
- Use a corrosion-resistant separation (heat exchanger) where gas-permeable plastic pipe is used, such as in underfloor heating.
- Where oxygen ingress is a risk, consider a sodium sulphite oxygen binder at 5 to 10 ppm.
- Keep the heating water pH between 8.2 and 9.5.
Damaged cables or lines
Viessmann · Boiler and external accessory cables
Damaged connecting cables or lines on the boiler or on externally installed accessories must be replaced with the correct parts.
- Replace damaged cables or lines with Viessmann cables or lines only.
- Have a qualified contractor make the replacement.
Dangerous conditions and emergency shutdown
Viessmann · Vitocrossal 300 CA3B
Use this sequence when the boiler or its power is in an unsafe condition.
- Deactivate main power immediately.
- Close the gas supply valve.
- If there is no gas smell, switch off the power at the separate fuse or disconnect switch.
- Use suitable extinguishers if there is a fire.
Dangerous conditions: emergency shutdown
Viessmann · Vitocrossal 300 CU3A, all models
If a dangerous condition exists, cut power and gas to the boiler before doing anything else.
- Deactivate the main power immediately.
- Close the gas supply valve.
Default pre-configuration of gateway
Viessmann · Versatronik 585 VI/BACIP
The gateway is set at the factory for eight Vitotronic 300 GW6B boilers and three heating zones.
- If you do not have eight GW6B boilers or three zones, change the configuration to match your system.
- Apply changes using the activate configuration steps.
Demonstration (trade fair) mode
Viessmann · Vitodens 100-W B1HE/B1KE
If the contractor has set the boiler to demonstration mode, for example at an exhibition, the boiler does not provide central heating, domestic hot water or frost protection.
- Check the main menu for the trade fair mode message.
- Have the contractor return the boiler to normal operation before relying on heat or hot water.
DHW 4th phase heating (auxiliary function)
Viessmann · Vitocrossal 300 CA3B
This heats the DHW tank to a second, higher DHW temperature during time phase 4. The heating contractor has to enable it by setting the second temperature.
- Have the heating contractor enable the second DHW set temperature.
- Set the start and stop times for time phase 4.
- Make sure start and stop times are also set for the 2nd and 3rd time phases.
DHW anti-Legionella boost function
Viessmann · Vitodens 200-W B2HB DHW tank
The boost heats the DHW tank to a second setpoint during the fourth time phase. It can act as an anti-Legionella function if DHW is not heated to 140°F (60°C) during the regular schedule. It is enabled by selecting a switching period for the fourth time phase. The boost differential is in coding level 2, address 59. The boost setpoint is in coding address 58.
- Select a switching period for the fourth time phase to enable the boost.
- Adjust the boost differential at coding level 2, address 59 if needed.
- Adjust the boost setpoint at coding address 58 if needed.
DHW booster heating
Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125
The booster heating function runs when a switching period is set for the fourth time phase. The boost temperature is set in coding address 58.
- Set the boost temperature in coding address 58.
DHW call for heat from a tank aquastat
Viessmann · Vitodens 100-W B1HE/B1KE
With a tank temperature switch (aquastat), the boiler target is the maximum permissible value for that boiler.
- No demand from the aquastat means no frost protection.
- Demand from the aquastat calls for the target value. There is no time program for DHW, no scald protection and no increased DHW hygiene in this case.
- Maximum DHW heating duration and minimum wait before the next DHW heating still apply. Check the system configuration parameter DHW.
DHW circulation pump operation
Viessmann · Heating systems with DHW circulation pump
With automatic mode, the DHW circulation pump runs alongside the DHW heating time program. Up to 4 individual time phases per day can be set instead, the same every day or different per day. The current program can be checked under Information, DHW. Only run the pump when DHW is actually drawn.
- Keep automatic mode for the pump, or set up to 4 individual time phases per day.
- To check the program, open Information and select the DHW group.
DHW circulation pump time program
Viessmann · Vitotronic 300-K, systems with DHW circulation pump
The circulation pump runs in parallel with the DHW heating program in automatic mode. Individual phases can be set instead. Only use circulation when DHW is actually drawn.
- Leave the pump in automatic mode to follow the DHW heating time program.
- For individual times, open the extended menu and select DHW.
- Select DHW circ time prog, then Individual.
- Select part of the week or a day, then the time phase.
- Set start and end times and press the exit key.
- Check the current program under Information, DHW group.
DHW fourth phase heating (auxiliary function)
Viessmann · DHW tank
This function heats the DHW tank to a second, higher DHW temperature. The heating contractor must enable it by setting a second DHW temperature. It runs during time phase 4. The 2nd and 3rd time phases must have a start and stop time set.
- Have the heating contractor set a second DHW temperature.
- Set the start and stop time for time phase 4.
DHW fourth time phase (second DHW temperature)
Viessmann · Vitotronic 300-K, MW2C
The heating contractor can enable a second, higher DHW setpoint. It runs during time phase 4. The 2nd and 3rd time phases need both a start and a stop time.
- Have the heating contractor set the second DHW temperature value.
- Set the start and stop times for time phase 4 in the DHW time program.
- Make sure start and stop times are set for time phases 2 and 3.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.