Viessmann Boiler: Connect the gateway to the boiler control
Connect the gateway to the boiler control on a Viessmann boiler: The supplied 3 ft (91 cm) CAT-5 cable joins the boiler control to the gateway. The control must have its LON communication card installed. Check the control's own manual for card location.
Applies to: Versatronik 511 with Vitotronic 100 GC1/GC1B, 300 GW2 or 300 GW5B
How to fix connect the gateway to the boiler control: step by step
- Confirm the LON communication card is installed in the boiler control.
- Plug one RJ45 end of the supplied CAT-5 cable into the control.
- Plug the other RJ45 end into the RJ45 socket inside the gateway.
- Wire the BMS LON 2-wire bus to terminals A and B.
- Connect the 120VAC plug-in power cord (120VAC unit).
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 511 & 511D LON Type B manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.