Viessmann Boiler: Connect the condensate drain
Connect the condensate drain on a Viessmann boiler: Route the condensate drain so it does not siphon the boiler, and ensure it can drain freely.
Applies to: CI2 399 to 2000
Common causes of connect the condensate drain
- Drain outlet below the boiler with no pump
- Drain connected to a shared or siphoning line
How to fix connect the condensate drain: step by step
- Install the condensate drain pipe with a suitable downward slope.
- Connect the drain with a P-trap or siphon.
- If the boiler condensate outlet is below the drain, install an approved condensing-boiler pump with an overflow switch.
- Terminate the drain into an open or vented drain as close to the boiler as possible.
- Do not connect other appliance drains, such as a water softener backwash, to this line.
- If using a neutralizing unit, discharge through it as required.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 installation instructions, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.