Viessmann Boiler: Condensate pump and discharge location
Condensate pump and discharge location on a Viessmann boiler: If the condensate outlet is lower than the drain, install a pump approved for condensing boilers with an overflow switch. The drain must end in an open or vented drain as close to the boiler as possible to prevent siphoning. Vent the tubing to atmosphere before a neutralization unit.
Applies to: Vitodens 200-W B2HA 80-100, 285-352
How to fix condensate pump and discharge location: step by step
- Install a condensing-approved pump with an overflow switch if the outlet is below the drain.
- Terminate the drain into an open or vented drain close to the boiler.
- Vent the discharge tubing to atmosphere before the neutralization unit, if used.
- Vent the pipe between the siphon trap and the neutralization unit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HA installation instructions, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.