Viessmann Boiler: Combustion values out of range
Combustion values out of range on a Viessmann boiler: CO2 or O2 reading is outside the target range.
Applies to: Vitocrossal 200 CI2
Common causes of combustion values out of range
- Leak in the flue gas or combustion air system
- Contaminated or damaged burner gauze assembly
- High flue gas side pressure drop due to contamination
How to fix combustion values out of range: step by step
- Check the flue gas and combustion air system for leaks.
- Check the burner gauze assembly for damage or contamination.
- Check the pressure drop on the flue gas side of the boiler for contamination.
- Re-measure CO and CO2/O2 after correction and record results on page 95.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.