Viessmann Boiler: Combustion faults caused by pulsation
Combustion faults caused by pulsation on a Viessmann boiler: Pulsating combustion can come from gas flow, air balance, condensate or flue problems.
Applies to: Vitocrossal 200 CI2
Common causes of combustion faults caused by pulsation
- Excessive gas throughput
- Insufficient or excessive combustion air
- Condensate drain in the flue system blocked
- Flue outlet not installed correctly
- Insufficient draught in the flue system
How to fix combustion faults caused by pulsation: step by step
- Adjust the gas throughput to match the rated boiler heating output.
- Correct the air settings.
- Check the condensate drain.
- Check the flue outlet and flue system.
- Check combustion in the installation room.
- Check the flue system for adequate draught.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Service Instructions, p. 75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.