Viessmann Boiler: Clear a maintenance message on Vitocontrol-S
Clear a maintenance message on Vitocontrol-S on a Viessmann boiler: A maintenance message from a connected Vitotronic 100 GC1 is shown on the Vitocontrol-S display. Acknowledge it here, then clear it on the Vitotronic. Button symbols are not legible in the text layer, so the key names are left out.
Applies to: Vitocontrol-S VD2/CT3/CM2 acting as fault manager (coding 79: 1)
How to fix clear a maintenance message on vitocontrol-s: step by step
- Open the maintenance display and scroll through the messages with the arrow keys.
- Select the acknowledge option and confirm that the display shows Acknowledge: Yes.
- Acknowledged messages can be shown again by holding the key for about 3 seconds.
- Acknowledge the maintenance message on the Vitotronic 100 GC1 (see page 107).
- If coding address 24 on the Vitotronic is not reset after maintenance, set it to 0 or the message returns the next Monday morning.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
More reset & cancel tips for boiler
Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 112. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.