Viessmann Boiler: Clean the condensate trap and drain pipe
Clean the condensate trap and drain pipe on a Viessmann boiler: Clean at least once a year.
Applies to: Vitocrossal 200 CI2
How to fix clean the condensate trap and drain pipe: step by step
- Disconnect the condensate drain pipe to the neutralizing system from the condensate trap.
- Unscrew the lower part of the condensate trap, remove the float and clear deposits.
- Clean all components.
- Reassemble the condensate trap and refit the drain pipe.
- If needed, clean the neutralizing system per its instructions.
- Make sure the hose does not sag; support it if needed.
- Check that condensate drains freely and operate the boiler only with the condensate trap fitted.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.