Viessmann Boiler: Clean the burner and gauze assembly
Clean the burner and gauze assembly on a Viessmann boiler: Cleaning and inspection of the burner. Same procedure for 399/500 and 750/1000 MBH burners, with the 750/1000 unit also having a burner baffle plate.
Applies to: Vitocrossal 200 CI2 burners
How to fix clean the burner and gauze assembly: step by step
- Remove the electrodes.
- Undo the 4 nuts and remove the burner gauze assembly, insulation sections and gaskets.
- Replace damaged components and use new gaskets.
- Reassemble in reverse order and tighten to the torque table for the burner size.
- Make sure the gasket between the fan housing and burner plate is seated correctly.
- If no parts are damaged, a visual check is enough; otherwise blow compressed air through the gauze assembly after detaching the fan.
- Clean the burner door from the outside with the gauze assembly facing up.
- Check for gas tightness after reassembly.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 29-30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.