Viessmann Boiler: Clean condensate trap
Clean condensate trap on a Viessmann boiler: Clean the condensate trap during regular maintenance. Blocked drainage makes condensate build up in the boiler and causes a burner shut-down with a fault message.
Applies to: Vitodens 200-W B2HA
How to fix clean condensate trap: step by step
- Remove the rubber cap below the condensate trap.
- Unscrew the threaded cap. It may need to be pried off.
- Clean out debris from the trap.
- Refit the threaded cap and rubber cap.
- Undo the union nut and pull the trap down off the boiler.
- Fill the trap with water.
- Reassemble in reverse order.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.