Other: Boiler tips (part 10 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Check operating data and burner runtime
Viessmann · Vitocrossal 200 CI2 boiler
Reads current output, hours run, burner runtime, burner starts and other data.
- Open the main menu and select Information.
- Select the data group.
- Retrieve the data.
Check system information
Viessmann · Control panel
Shows current system data such as temperatures. Groups: General, Burner, DHW, Heating circuit 1 to 4, Heating zones 1 to 4, Contractor contact details, Internet, Open source licence, Cascade and Cascade boilers. Named heating circuits and zones show their assigned names.
- Open Information.
- Select the required group.
Check system information (temperatures and pump data)
Viessmann · System information
Shows current system data such as temperatures, including temperature controller and heating circuit pump information. Detailed groups are in the menu overview.
- Call up the home screen.
- Select Information, then confirm with OK.
- Select the required group, then confirm with OK.
- Select the required information.
- Press and hold the exit button for about 4 sec to leave the menu.
Checking live values under the Information menu
Viessmann · Vitocrossal 300 CU3A boilers with Vitotronic 200 KW6B control
The Information menu lets you scan live readings and status. Under General it lists outside temperature, boiler temperature, flue gas temperature, sensor 9, burner status, operating hours and per-stage hours run, fuel consumption, feed pump, and the compiled fault message. Under Solar, DHW and each heating circuit it lists temperatures, pump and valve status, time programs and operating status. Which scans appear depends on the equipment fitted, so some may be missing.
- Open the extended menu and select Information.
- Pick the group you need: General, DHW, Solar, or the heating circuit.
- Scroll the list and read the value or status shown.
Chemicals not to store near boiler
Viessmann · Boiler room storage
Chemicals in the air can form poisonous and corrosive combustion by-products. Keep these away from the boiler and boiler room.
- Do not store chlorine products, bleach, cleaning solvents, detergents, acids, hair spray, spray cans, paint thinners, paint, water softener salt, perchloroethylene, or carbon tetrachloride near the boiler.
Chilled water and cooling season valve changeover
Viessmann · Vitocrossal 200 CI2 with chilled water or refrigeration system
With a refrigeration system, pipe the chilled medium in parallel with the boiler and fit valves so chilled water cannot enter the boiler. Flow control valves or other automatic means must stop gravity circulation of boiler water during cooling. The boiler circulating pump must run from its own on/off switch, not from the boiler control. Valves V1 and V2 are changed over by season, and metal tags should label them.
- Pipe the chilled medium in parallel with the boiler.
- Install valves so chilled water cannot enter the boiler.
- Install flow control valves or equivalent to prevent gravity circulation during cooling.
- Power the circulating pump from a separate on/off switch, not the boiler control.
- Cooling season: close valve V1 and open valve V2.
- Heating season: close valve V2 and open valve V1.
- Attach metal tags to label valves V1 and V2.
Chimney and draft regulator requirements
Viessmann · Vitorond 200 VD2A boiler
The boiler is not approved for side wall venting. The chimney must be designed for the relatively cool flue gases. Vent collar diameter does not set chimney size. Insulate the connection length between the vent collar and chimney. If a calculated diameter falls between two sizes, use the larger one.
- Do not vent through a side wall. Vent all products of combustion to the outdoors.
- Insulate the chimney connection between the vent collar and the chimney.
- Install a barometric draft regulator in the chimney or vent 5 to 7 ft. (1.5 to 2 m) from the breeching outlet at the rear of the boiler.
- Do not stand on the top panel when installing or insulating overhead piping or venting.
Chimney sizing and intermediate venting
Viessmann · Chimney venting
Chimney must be sized for the flue gas temperatures this boiler produces. Oversized, poorly insulated chimneys let gases cool and condense. If the calculated diameter falls between two sizes, use the larger.
- Keep the intermediate vent section the same diameter as the boiler vent collar.
- Keep the path between boiler and chimney as short as possible, with no more than two elbows.
- Avoid two level 90° elbows in a row.
- Seal the intermediate section pressure tight at the boiler collar and chimney connection, including any combustion test ports.
- Install a barometric damper.
Choose an operating program when heat or hot water is not needed
Viessmann · Vitocrossal 300 CU3A
Operating programs reduce energy use when full heating is not required.
- For summer with hot water only, select "Only DHW".
- If the home needs no heat and no hot water for longer periods, select "Standby mode".
- For a short absence, select "Economy mode" to reduce room temperature.
- For a longer absence, select the "Holiday program", which lowers room temperature and turns off DHW heating.
Circuit diagrams are recommendations only
Viessmann · All circuit diagrams 5 to 9
The circuit diagrams are recommendations. The customer or heating contractor must confirm the design is complete and fully functional.
- Check the hydraulic and electrical design is complete and functional before final commissioning.
Circulation pump exercise function
Viessmann · Circulation pumps
Circulation pumps run for 10 seconds every 24 hours to stop them seizing. This runs in all operating programs and during warm weather shutdown.
Circulation pump wiring
Viessmann · Vitotronic 300 KW3 with circulation pumps
Use only Viessmann pre-wired plug-in pumps on the Power Pump Module. If pre-wired pumps are used, do not also connect a pump to the hard-wired terminals of the same circuit.
- Insert the supplied strain relief through the Power Pump Module knockout and fasten with the nut.
- Connect the Rast-5 connector to the matching plug-in terminal on the Power Pump Module.
- For hard-wired 120 VAC pumps, connect to the terminal strip of the Power Pump Module.
Circulator type with zone valves
Viessmann · Vitocrossal CU3A zoned systems
Single-speed circulators need a pressure differential bypass so flow does not rise when one zone valve opens. Variable-speed circulators adjust automatically as zones open and close.
- With a single-speed circulator, install a pressure differential bypass.
- With a variable-speed circulator, no bypass is needed for flow adjustment.
Clean condensate trap
Viessmann · Vitodens 200-W B2HA
Clean the condensate trap during regular maintenance. Blocked drainage makes condensate build up in the boiler and causes a burner shut-down with a fault message.
- Remove the rubber cap below the condensate trap.
- Unscrew the threaded cap. It may need to be pried off.
- Clean out debris from the trap.
- Refit the threaded cap and rubber cap.
- Undo the union nut and pull the trap down off the boiler.
- Fill the trap with water.
- Reassemble in reverse order.
Cleaning the control
Viessmann · Vitotronic 300-K MW1B / Vitotronic 100 GC1B
Equipment can be cleaned with a commercially available non-scouring domestic cleaner.
- Clean the front of the programming unit with a microfibre cloth
Cleaning the devices
Viessmann · Vitotronic 200-H, Model HK1M
All devices can be cleaned with a commercially available domestic cleaning agent. Use a non-scouring product.
- Clean with a domestic non-scouring cleaning agent only.
Cleaning the equipment
Viessmann · Vitocontrol-S VD2/CT3/CM2
Clean the outside of the equipment with suitable cleaning agents.
- Use domestic cleaning agents available on the market.
- Do not use abrasive cleaning agents.
Cleaning the remote control
Viessmann · Vitotrol 300A
The unit can be cleaned with a commercially available household cleaner that is not scouring.
- Use a non-scouring domestic cleaning agent.
Clear maintenance display
Viessmann · Maintenance and service messages
The maintenance message is confirmed from the home screen. If several faults are active, a list of service messages appears in yellow.
- Tap Confirm on the maintenance display.
- If several fault messages exist, tap Service messages to view the yellow list.
Clear the maintenance display
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
When the service limit is reached, Service and a symbol appear on the display. Several fault messages can be listed under Service messages.
- Tap Confirm on the maintenance display.
- If several messages are active, tap Service messages to view the list.
- Carry out the maintenance and reset the service interval.
Clearance from hot water pipes to combustible construction
Viessmann · Vitodens 200-W B2HB
Keep at least 2 in. (51 mm) clearance around non-insulated hot water pipes to combustible construction. Insulated pipes may be reduced to 0 in. if the insulation thickness and value are sufficient, per local gas codes.
- Keep a minimum 2 in. (51 mm) clearance around non-insulated hot water pipes.
- If the pipe is insulated to the required thickness and value, check local gas codes before reducing clearance to 0 in.
Clearance from uninsulated hot water pipes
Viessmann · Heating and DHW piping
Uninsulated hot water pipes need clearance from combustible materials. Insulation of adequate thickness removes the need for it.
- Keep at least 2 in. (50 mm) from uninsulated hot water pipes to combustible components.
- Follow local gas regulations for insulated pipes.
Clearance from uninsulated hot water piping
Viessmann · Piping layout near combustible construction
Keep at least 2 in. (51 mm) all around uninsulated hot water pipes to combustible construction. With suitable pipe insulation the clearance can drop to 0 in., but check local gas code first.
- Measure clearance around each uninsulated hot water pipe to combustible material.
- If pipes are insulated, confirm insulation thickness and value are adequate, then check local gas code before reducing clearance.
Clearances to combustibles
Viessmann · Piping clearances
Clearance from non-insulated hot water pipes to combustible construction is 2 in minimum. Insulated pipes with adequate insulation may be reduced to 0 in.
Closing the control unit cover
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Final steps to close the boiler control unit.
- Install the cover onto the control board.
- Flip the control board back into position.
- Secure the locking tabs as shown.
Closing the external accessory connection box
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Closing and securing the external accessory connection box cover and retaining screw.
- Tilt the top of the external accessory connection box cover forward.
- Drop the cover down over the locating pins and set it in place.
- Swing the external accessory connection box up.
- Push the box in until the holding screw is in place.
- Tighten the external accessory connection box retaining screw.
- Install the external accessory connection box cover screws.
CO and gas tightness checks
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
Incorrect burner adjustment can cause dangerous CO build-up. Gas leaks at the test nipple are an explosion risk.
- Carry out a CO test before and after any work on the gas appliance.
- Check gas tightness at test nipple A using a soap and water solution.
- Never use a flame or match to check for leaks.
- Never purge a gas line into the combustion chamber.
CO2 measurement required around gas work
Viessmann · Vitocrossal 200 CI2
A CO2 measurement must be taken before and after working on gas appliances to check the combustion condition.
- Measure CO2 before working on the gas appliance.
- Measure CO2 again after the work is done.
- Refer to page 25 for the measurement procedure.
Code references for combustion air and venting
Viessmann · VR1 22 to 33, 91 to 140
Canada: CSA B139-00 (oil installations) and CAN/CSA-A405 for chimney construction. US: NFPA 31 (oil burning equipment) and NFPA 211 (chimneys, vents). Always use the latest editions.
Codes and wiring requirements
Viessmann · Vitorond 100 installation
Installation must follow local codes. Where none apply, use CAN/CSA-B139.00 for oil installations in Canada. Electrical wiring follows CSA C22.1 Part 1 or local codes, and NEC ANSI/NFPA 70 in the U.S. Controls must also meet ANSI/ASME CSD-1 where the authority having jurisdiction requires it.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.