Viessmann Boiler: Clean condensate drain pipe and condensate trap
Clean condensate drain pipe and condensate trap on a Viessmann boiler: Clean the inside of the condensate drain pipe and condensate trap at least once a year.
Applies to: Vitocrossal 200 CI2 boilers
Common causes of clean condensate drain pipe and condensate trap
- Deposits building up in the condensate trap or drain pipe
How to fix clean condensate drain pipe and condensate trap: step by step
- Disconnect the condensate drain pipe to the neutralizing system from the condensate trap.
- Unscrew the lower part of the condensate trap. Remove the float and deposits, then clean the components.
- Reassemble the condensate trap.
- Refit the condensate drain pipe.
- If needed, clean the neutralizing system per the manufacturer's instructions.
- Confirm the condensate drains freely before operating the boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Service Instructions, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.