Viessmann Boiler: Clean combustion chamber and heat exchanger
Clean combustion chamber and heat exchanger on a Viessmann boiler: Clean the stainless steel heat exchanger without chemicals. Keep water away from the refractory.
Applies to: Vitocrossal 200 CM2 186 to 311
How to fix clean combustion chamber and heat exchanger: step by step
- Vacuum loose debris out of the combustion chamber.
- Rinse embedded sediment from the stainless steel heat exchanger with water or a solvent-free cleaner such as citric acid based cleaner.
- Use a non-metallic brush with gentle strokes if needed.
- Flush the combustion chamber with water until it runs clear through the condensate trap.
- Clean out debris from the condensate trap and reinstall it.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.