Viessmann Boiler: Chimney sizing and intermediate venting
Chimney sizing and intermediate venting on a Viessmann boiler: Chimney must be sized for the flue gas temperatures this boiler produces. Oversized, poorly insulated chimneys let gases cool and condense. If the calculated diameter falls between two sizes, use the larger.
Applies to: Chimney venting
How to fix chimney sizing and intermediate venting: step by step
- Keep the intermediate vent section the same diameter as the boiler vent collar.
- Keep the path between boiler and chimney as short as possible, with no more than two elbows.
- Avoid two level 90° elbows in a row.
- Seal the intermediate section pressure tight at the boiler collar and chimney connection, including any combustion test ports.
- Install a barometric damper.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100, VR1 Technical Data, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.