Viessmann Boiler: Chimney and draft regulator requirements
Chimney and draft regulator requirements on a Viessmann boiler: The boiler is not approved for side wall venting. The chimney must be designed for the relatively cool flue gases. Vent collar diameter does not set chimney size. Insulate the connection length between the vent collar and chimney. If a calculated diameter falls between two sizes, use the larger one.
Applies to: Vitorond 200 VD2A boiler
How to fix chimney and draft regulator requirements: step by step
- Do not vent through a side wall. Vent all products of combustion to the outdoors.
- Insulate the chimney connection between the vent collar and the chimney.
- Install a barometric draft regulator in the chimney or vent 5 to 7 ft. (1.5 to 2 m) from the breeching outlet at the rear of the boiler.
- Do not stand on the top panel when installing or insulating overhead piping or venting.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200, VD2A Series Installation, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.