Viessmann Boiler: Checking the DHW flow limiter and filter (gas condensing combi)
Checking the DHW flow limiter and filter (gas condensing combi) on a Viessmann boiler: Inspect and clean or replace the DHW flow limiter and sieve on the combi boiler. Drain the DHW side first.
Applies to: B1KE 120, B1KE 199
Common causes of checking the dhw flow limiter and filter (gas condensing combi)
- Scaling on the flow limiter
- Damage to the flow limiter or sieve
How to fix checking the dhw flow limiter and filter (gas condensing combi): step by step
- Remove the control unit and the burner, then drain the boiler on the DHW side.
- Remove the spring clip. On a B1KE-199, undo the G 3/4 inch union nut at the cold water inlet and the union nut on the upper side of the flow sensor, then pull the pipe out.
- Remove the DHW flow sensor.
- Check flow limiter A and filter sieve B. Replace them if scaled or damaged, then reinsert.
- Refit the DHW flow sensor with new gaskets in reverse order. Tighten the union nuts to 18 lb.ft (24 Nm).
- Check all water side connections for tightness.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.