Viessmann Boiler: Checking static and supply pressure
Checking static and supply pressure on a Viessmann boiler: Measure gas static pressure and running (supply) pressure at the test nipple. Do not adjust the inlet pressure switch; it is factory set to 4 in. w.c.
Applies to: Vitocrossal 200 CM2 186 to 311 boilers
How to fix checking static and supply pressure: step by step
- Close the gas shut-off valve.
- Undo the screw inside test nipple A. Do not remove it.
- Connect the pressure tester at test nipple A.
- Open the gas shut-off valve.
- Check the static pressure (maximum 14 in. w.c.).
- Record the value in the Maintenance Record.
- Start the burner at maximum output using the emissions test switch.
- Measure the supply pressure with a gauge that resolves at least 0.04 in. w.c.
- Record the value in the report.
- Close the gas shut-off valve.
- Remove the pressure tester and close test nipple A.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, pp. 14-15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.