Viessmann Boiler: Checking CO2 level at upper heating input
Checking CO2 level at upper heating input on a Viessmann boiler: Set the burner to maximum output and check CO2 at the flue pipe. Adjust only if outside range.
Applies to: Vitocrossal 200 CM2 186 to 311 boilers
How to fix checking co2 level at upper heating input: step by step
- Start the burner with the emissions test switch enabled.
- Press button Y or E until the service display shows 100 (100%).
- Check the CO2 level at the flue pipe.
- If adjustment is needed, remove cap B.
- Turn adjusting screw A in small steps with a 3 mm Allen key.
- Turning clockwise lowers CO2 (less gas). Turning counter-clockwise raises CO2 (more gas).
- Record the actual value in the report on page 64.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.