Viessmann Boiler: Check static gas pressure
Check static gas pressure on a Viessmann boiler: Confirm the static gas pressure at the inlet test connector. Maximum is 14 in w.c.
Applies to: Vitocrossal 200 CI2 399 to 2000 MBH
How to fix check static gas pressure: step by step
- Close the gas shut-off valve.
- Loosen the screw in test connector A without removing it.
- Connect the pressure gauge to test connector A.
- Open the gas shut-off valve.
- Check that static pressure is no more than 14 in w.c.
- Record the reading on the maintenance record (page 95).
- Check all connections for gas tightness with soap and water.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.