Viessmann Boiler: Check running supply pressure (NG or LPG)
Check running supply pressure (NG or LPG) on a Viessmann boiler: Measure supply pressure with the burner at maximum output. Use a gauge with at least 0.04 in w.c. resolution. Do not open any flame near the boiler.
Applies to: Vitocrossal 200 CI2 399 to 2000 MBH
How to fix check running supply pressure (ng or lpg): step by step
- Start the burner.
- Set the burner to maximum heating output using the actuator test at maximum heat input in the service menu. Parameter 596 sets the target but is not applied in the actuator test.
- Measure the running supply pressure and compare with the pressure table.
- Record the actual value on the maintenance record (page 95).
- Close the gas shut-off valve.
- Remove the pressure tester and close test nipple A.
- Check for leaks with soap and water only. Never use matches, candles or flame, and never purge gas into the combustion chamber.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.