Viessmann Boiler: Check power pump module fuse F1
Check power pump module fuse F1 on a Viessmann boiler: Check the fuse on the power pump module.
Applies to: Power pump module fuse F1 T6.3A
How to fix check power pump module fuse f1: step by step
- Switch off the main power supply. The boiler ON/OFF switch does not disconnect power to the power pump module, so the main service switch or breaker must be turned off.
- Flip down and remove the control unit.
- Remove the power pump module cover plate.
- Check fuse F1, T6.3A slow blow.
- Replacement fuses come from Viessmann in packs of 10 (Part No. 7815 580).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.