Viessmann Boiler: Check or replace the plate type heat exchanger (CombiPLUS)
Check or replace the plate type heat exchanger (CombiPLUS) on a Viessmann boiler: Check the DHW side for scale and the heating water side for contamination. Clean or replace the plate type heat exchanger as needed.
Applies to: CombiPLUS plate type heat exchanger
Common causes of check or replace the plate type heat exchanger (combiplus)
- Scaling on the DHW side
- Contamination on the heating water side
How to fix check or replace the plate type heat exchanger (combiplus): step by step
- Shut off and drain the boiler on the heating water and DHW sides.
- Disconnect the diverting valve motor connection.
- Push the three-way valve drive A slightly upwards.
- Turn the three-way valve B with drive A 1/8 turn counterclockwise and remove it.
- Remove the two screws C from the plate type heat exchanger and remove the heat exchanger D with its gaskets. Small amounts of water may trickle out.
- Check the DHW side for scaling. Clean or replace the heat exchanger if required.
- Check the heating water side for contamination. Clean or replace the heat exchanger if required.
- Install in reverse order with new gaskets. Refer to the installation instructions for additional mounting options.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.