Viessmann Boiler: Check flue side gaskets and seals
Check flue side gaskets and seals on a Viessmann boiler: Check the flue gas collector seal to the boiler. Leaks show as condensate on the outside of the collector.
Applies to: Vitocrossal 200 CM2 186 to 311
Common causes of check flue side gaskets and seals
- Loose flue gas collector fasteners
- Damaged gasket
How to fix check flue side gaskets and seals: step by step
- Remove rear panels and disconnect the venting from the flue gas collector.
- Check that flue gas collector C is tight to boiler A. Retighten mounting fasteners D if needed.
- Reconnect the venting with the flue gas pipe adaptor and tighten with gear clamps.
- Check the flue coupling for leaks with a certified leak detector.
- Check seals under full load with an inspection mirror if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.