Viessmann Boiler: Check flue side for leaks
Check flue side for leaks on a Viessmann boiler: Check the flue gas collector, boiler body and gaskets for leaks. Use a dew point hygrometer at full load. Condensed water on the outside of the flue gas collector or thermal insulation also indicates a leak. Detach thermal insulation parts if needed.
Applies to: Vitocrossal 200 CI2 boilers
Common causes of check flue side for leaks
- Failed flue gas collector gasket or boiler body seal
How to fix check flue side for leaks: step by step
- Run the boiler at full load.
- Check the flue gas collector and boiler body for leakage with a dew point hygrometer.
- Look for condensed water on the outside of the flue gas collector or on insulation.
- Check the burner door gasket for correct seating.
- After the burner is removed, finish with a CO2 test per the page 26 points and record the values in the report on page 95.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Service Instructions, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.