Viessmann Boiler: Check expansion tank and system pressure
Check expansion tank and system pressure on a Viessmann boiler: Check the diaphragm expansion tank pressure against the static water fill pressure on a cold system.
Applies to: Diaphragm expansion tank
Common causes of check expansion tank and system pressure
- Cyclical pressure swings or large pressure differences indicate a system fault.
How to fix check expansion tank and system pressure: step by step
- Carry out this test on a cold system.
- Drain the system or close the cap valve on the diaphragm expansion tank.
- Reduce the pressure until the gauge reads 0.
- Check that the 60 F (15.5 C) water fill pressure equals the expansion tank pressure.
- Follow the expansion tank manufacturer's instructions.
- Fix any pressure fault right away to protect the other system components.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.