Viessmann Boiler: Check and adjust CO2 at upper heating input
Check and adjust CO2 at upper heating input on a Viessmann boiler: Set the boiler to full load and adjust CO2 with the gas valve adjusting screw.
Applies to: Vitocrossal 200 CM2 186 to 311
How to fix check and adjust co2 at upper heating input: step by step
- Press the Y E button until the service display reads 100 (100 %).
- Measure CO2 at the flue pipe.
- If CO2 is outside the table range, remove cap B.
- Turn adjusting screw A with a 3 mm Allen key in small steps. Clockwise lowers CO2 (less gas). Counter-clockwise raises CO2 (more gas).
- Record the actual value on the maintenance record (page 64).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.