Viessmann Boiler: Change AUX input mode to 0-10 VDC
Change AUX input mode to 0-10 VDC on a Viessmann boiler: The AUX input is set to DEMAND from the factory and must be changed to 0-10 VDC for BMS control.
Applies to: Versatronik 300 Cascade Control, AUX input
How to fix change aux input mode to 0-10 vdc: step by step
- Press and hold ENTER for 5 seconds.
- Press the up arrow until Specifications appears and press ENTER.
- Press the up arrow until AUX Mode shows and press ENTER to set 0-10 VDC mode.
- Press ESC to exit to the set point screen.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More settings shortcuts tips for boiler
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.