Settings shortcuts: Boiler tips (part 2 of 10)
Short, practical technician tips on settings shortcuts for boiler. Check each one against the manual for your exact model before acting.
Switch DHW comfort mode (Eco or Comfort)
Rinnai · I-Series Plus condensing combi boiler, controller
Eco mode is the default and saves energy but gives slower hot water. Comfort mode keeps the primary heat exchanger warm for faster hot water and uses more energy. The Eco icon is always on during DHW recirculation.
- Press the Settings button.
- Use the Up or Down arrows to select the unit for Eco mode.
- Set On for Eco mode or OFF for Comfort mode.
- To enable Comfort mode, press the Eco button on the controller.
Turn the control panel click sound on or off
Rinnai · I-Series Plus condensing combi boiler, controller
Turns the key click sound on the controller on or off.
- Press the Select button.
- Press the Mode button twice. The display shows 2:on.
- Use the Up or Down arrows to select ON or OFF.
- Press Select to confirm.
Access outdoor reset menu and adjust slope, shift, WWSD
Viessmann · Versatronik 300 cascade control
Outdoor reset must be enabled to use slope, shift and WWSD. Slope, shift and WWSD are the three adjustments.
- Press and hold ENTER for about 5 seconds.
- Use the arrow up or down key to select the Outdoor Reset menu.
- Press ENTER to select the value to change. EDIT appears on the screen.
- Use the arrow keys to set the new value.
- Press ENTER to accept the value, or ESC to exit to the main menu.
Access the standard and extended menus
Viessmann · Programming unit navigation
The standard menu has the frequent settings. The extended menu has less-used settings such as time and holiday programs.
- If the screen saver is on, press any key except the one marked ? to wake the display.
- To reach the standard menu from elsewhere in the menu, keep pressing the back key until it appears.
- To reach the extended menu from the screen saver, press any key except ?, then press the key shown in the manual (not legible in extract).
- To reach the extended menu from elsewhere in the menu, press the key shown in the manual (not legible in extract).
Activate and end comfort (party) mode
Viessmann · Vitotrol 200A remote control
Temporarily changes the room temperature for several hours. DHW is boosted to the temperature set at the Vitotronic control unit. A changed room temperature is kept after party mode ends.
- To use a different room temperature, first set it with +/- and confirm with OK.
- Press the party mode key to start comfort mode.
- To end it early, press the party mode key again.
- Otherwise it ends automatically after 8 hours, or when the system switches to standard heating mode under the time program on the Vitotronic.
Activate and end economy mode
Viessmann · Vitotrol 200A remote control
Lowers the room temperature during standard heating mode to save energy. The economy symbol must be visible in the display.
- Press the economy mode key to start economy mode.
- Press the economy mode key again to end it.
- Otherwise it ends automatically when the system switches to reduced heating mode under the time program on the Vitotronic.
Activate economy mode
Viessmann · Vitotronic 300-K, MW1B
Lowers the room temperature during standard heating mode to save energy, for example when the building is empty for a few hours.
- Open the extended menu.
- Select "Heating".
- Select the heating circuit if needed.
- Select "Economy mode".
Activate energy saving mode
Viessmann · Vitotronic 300 Model GW2
Only available in the 'rw' heating program. Lowers the preset room temperature for a short time to heat more economically.
- Press the heating circuit selector button so it lights up.
- Press the energy saving button; the button lights and the energy saving display shows briefly.
Activate party mode
Viessmann · Vitotronic 300 Model GW2
Gives heating and domestic hot water (if a DHW tank is fitted) for a short time, independent of the preset heating and time programs.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button so it lights up.
- Press the party mode button; the party display appears and the party temperature flashes.
- Press the up or down button to change the party temperature if needed.
- Press OK to confirm and store the value.
- Close the hinged cover.
Activate the holiday program
Viessmann · Heating circuits and DHW heating
Holiday mode runs from 00:00 on the first day to 23:59 on the last day. Heating circuits in Heating mode drop to the reduced temperature. Circuits in Standby keep only frost protection. DHW heating is off, with frost protection active. In Apartment building mode, DHW stays on unless all circuits are in holiday mode. Not available for heating zones or for systems with a DHW tank with temperature switch (such as an Aquastat).
- Open the Holiday program function.
- Select the heating circuit.
- Set the First holiday and Last holiday dates.
- Confirm.
- To switch off, open Holiday program, select the heating circuit, and deselect.
Adjust display backlighting
Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C
Sets brightness separately for standby and for control use.
- From the home screen, open Menu, then Settings.
- Open Screen.
- Select Brightness standby or Brightness control.
- Choose the required value.
- Press OK to confirm.
Adjust display contrast and brightness
Viessmann · Vitotronic 300-K, MW1B only
Changes display contrast, and brightness for the control texts or the screen saver.
- Open the extended menu.
- Select "Settings".
- Select "Contrast" and set the value, or select "Brightness".
- For brightness, choose "Control" to make menu text clearer, or "Screen saver" to change the screen saver brightness.
- Set the required brightness.
Adjust display contrast on Vitocontrol-S
Viessmann · Vitocontrol-S VD2/CT3/CM2 control unit
The display contrast can be darkened or lightened with button combinations.
- Press OK and + together to darken the display.
- Press OK and - together to lighten the display.
Adjust heating curve slope and shift for a heating circuit
Viessmann · Vitotronic 300 GW6B boiler control unit, all heating circuits
Slope and shift are set separately for each heating circuit. Shift moves the curve up or down in parallel. The example graph on the page is not transcribed here.
- From the home screen, tap Menu.
- Choose Heating circuit 1, 2 or 3.
- Tap Heating.
- Tap Heating curve.
- Use +/- to set the required Slope or Shift value.
- Tap OK to confirm.
Adjust normal and reduced room temperature
Viessmann · Vitotronic 200-H heating circuit
Normal (day) room temperature is chosen with the rotary dial and is applied automatically after about 2 seconds. Reduced (night) room temperature is set separately.
- For normal room temperature, turn the rotary dial to the desired day temperature.
- For reduced room temperature, press the night temperature button (symbol not legible in the source).
- Change the value with the up or down arrow.
- Confirm with OK.
- Example: changing normal temperature from 20°C to 26°C / 68°F to 79°F; changing reduced temperature from 5°C to 14°C / 41°F to 57°F.
Adjust room temperature and heating program in the standard menu
Viessmann · Vitocrossal 300 CU3A with Vitotronic control
The standard menu covers the most-used settings for the heating circuit shown in the header. Heating programs are standby with frost protection, DHW only, and heating plus DHW. The display returns to the standard menu about 2 minutes after the last change.
- Set the room temperature with the arrow keys, then press OK to confirm.
- Select the heating program with the arrow keys, then press OK to confirm.
Adjust room temperature setback
Viessmann · Heating circuits with room temperature control
Example from the manual: changing the setback from 41 F to 57 F (5 C to 14 C). Steps 1 and 8 are not legible in the text.
- Select 'Heating'.
- Select the heating circuit.
- Press OK.
- Select the red room temperature setpoint (setback), then press OK.
- Change the value with the arrow keys.
- Accept with OK.
Adjust room temperature setpoint
Viessmann · Heating circuits with room temperature control
Example from the manual: changing the setpoint from 68 F to 79 F (20 C to 26 C). Steps 1 and 8 are not legible in the text.
- Select 'Heating'.
- Select the heating circuit.
- Press OK.
- Select 'Room temperature setpoint', then press OK.
- Change the value with the arrow keys.
- Accept with OK.
Adjust the heating curve slope and shift
Viessmann · Weather-compensated operation
Adjust slope and shift in weather-compensated operation. The graph updates as you change the values.
- Open the "Heating" function.
- Select the heating zone or heating circuit.
- Open "Heating curve".
- Set the required Slope and Shift values.
- Confirm.
Adjusting display contrast
Viessmann · HK1S and HK3S
Contrast of the display window can be changed from the programming unit.
- Open the hinged cover on the programming unit.
- Hold the contrast key and press the up or down button at the same time to adjust contrast.
Boost heating and rapid setback
Viessmann · HK1S, HK3S
Temporary room temperature changes that stop when the set room temperature is reached.
- Boost heating: raise set room temperature by at least 2 K with the party key. It also starts on change from reduced to standard temperature and at start-up optimisation.
- Rapid setback: lower set room temperature by at least 2 K with the energy saving key. It also starts on change from standard to reduced temperature and at shut-down optimisation.
Button use: scrolling, editing and exiting
Viessmann · Versatronik 300 user interface
The control has four buttons: ESC, Arrow Up, Arrow Down and ENTER. Arrows scroll screens and menu items. ENTER opens the menu and edits values.
- Use UP and DOWN to scroll the main screens or menu items.
- Press ENTER on a setting to edit it.
- Press ENTER again to make the new value take effect.
- Press ESC to exit a screen or menu and return to the ST (supply temperature) screen.
Call up and change coding 1 addresses
Viessmann · Vitotronic 200-H coding 1
Method for coding 1. Key symbols were not legible in the extracted text.
- Press the 9 and w keys together for about 2 seconds.
- Select the coding address with the up or down key; the address flashes. Confirm to show the value.
- Change the value with the up or down key and confirm.
- The display briefly shows 'Accepted', then the address flashes again.
- Select further addresses with the up or down key.
- To exit, press the 9 and w keys together for about 1 second.
Call up coding 1
Viessmann · Vitotronic 100 GC1 coding 1
Entry to the coding 1 address list.
- Press 9 and w together for about two seconds, until the first arrow appears in the display.
- Select the coding address with the up or down arrow; the address flashes. Confirm to make the value flash.
- Change the value with the up or down arrow and confirm. The value is stored and stops flashing after about 2 seconds.
- Select further addresses with the arrows.
- Press 9 and w together for about one second to exit.
Call up coding 2
Viessmann · Vitotronic 100 GC1 coding 2
Entry to the coding 2 address list.
- Press w and rw together for about two seconds, until the first two arrows appear in the display; confirm.
- Select the coding address with the up or down arrow; the address flashes. Confirm to make the value flash.
- Change the value with the up or down arrow and confirm. The value is saved and stops flashing after about 2 seconds.
- Select further addresses with the arrows.
- Press w and rw together for about one second to exit.
Calling up system configuration parameters
Viessmann · Vitodens 100-W
Route to the parameter groups General, Boiler and DHW. Parameters can also be set with the Vitoguide mobile software tool.
- Open the service menu with the button combination.
- Select System configuration and press OK.
- Select the required group (General, Boiler or DHW) and press OK.
- Select the parameter, press OK, set the value and press OK to confirm.
Calling up the main menu on the programming unit
Viessmann · Vitocrossal 300 CA3B Dual Fuel programming unit and service display
The main menu gives access to all settings, scans, heating defaults and time programs available at the system and lead control unit. The footer buttons return to the home screen, go back one menu level or cancel a setting, open help text, show fault or service messages, and scroll the menu.
- If the screensaver is on, tap the display, then tap Menu.
- From anywhere in the menu, tap the menu button, then tap Menu.
- Use the footer buttons to go home, go back, open help, view faults or service messages, or scroll.
Central control of heating circuits
Viessmann · Multiple heating circuits on one system
Coding 7a in the General group sets one heating circuit as the central control. Its operating and holiday program then applies to all other heating circuits. Those circuits show 'Central control' on the display. Any holiday programs already set on them are deleted. Party and economy modes cannot be enabled on every control unit.
- Set coding 7a in the General group to program central control to one heating circuit.
- Check the other circuits show 'Central control' to confirm.
Change and save advanced parameters
Viessmann · Vitotron 100 VLN2
Move through the parameters with the right arrow, change values with the up and down arrows, then save by leaving advanced settings.
- Use the up and down arrows (5, 6) to select the value you want.
- Press the right arrow button (4) to move to the next parameter.
- When finished, press and hold the power button (9) until the display returns to blank stand-by with the intermittent red dot.
- Press the power button (9) to turn the boiler back on.
Change AUX input mode to 0-10 VDC
Viessmann · Versatronik 300 Cascade Control, AUX input
The AUX input is set to DEMAND from the factory and must be changed to 0-10 VDC for BMS control.
- Press and hold ENTER for 5 seconds.
- Press the up arrow until Specifications appears and press ENTER.
- Press the up arrow until AUX Mode shows and press ENTER to set 0-10 VDC mode.
- Press ESC to exit to the set point screen.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.