Viessmann Boiler: Category III positive pressure venting
Category III positive pressure venting on a Viessmann boiler: The Vitorond 200 is a Category III positive pressure non-condensing boiler and must be vented individually. The vent must be gas tight and use a suitable stainless steel system listed for Category III.
Applies to: Vitorond 200 boiler, Category III
How to fix category iii positive pressure venting: step by step
- Use an AL29-4C special stainless steel venting system listed for Category III for single-wall vertical venting.
- Connect the flue outlet with the shortest run, a slight upward slope to the stack, and no sharp bends. Flue outlet outside diameter is 8 in. (200 mm).
- Drill a 10 mm test hole in the side of the vent pipe about two to three vent diameters from the flue collar.
- Seal and insulate the vent pipe.
- Follow the Viessmann positive pressure venting system instructions for details.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200, VD2A Series Installation, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.