Other: Boiler tips (part 9 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Carbon monoxide alarm before startup
Viessmann · Vitocrossal 200 CI2 installations in residential buildings
A carbon monoxide alarm must be in place in any residential living space before the appliance is started.
- Install at least one carbon monoxide alarm in the residential living space or home.
- Follow the alarm maker's instructions and local codes.
- Confirm the alarm is installed before putting the boiler into operation.
Carbon monoxide alarm requirement
Viessmann · Vitocrossal 300 CA3B
Carbon monoxide can be produced by incomplete combustion. The installer must confirm an alarm is in place before start-up.
- Confirm at least one carbon monoxide alarm is installed in the living space before the boiler is put into operation.
- Install, maintain and replace alarms per the alarm maker's instructions and local codes.
Carbon monoxide and venting
Viessmann · Vitotronic 200 and 300-K
Improper installation, adjustment, service or maintenance can let flue gas, which contains carbon monoxide, enter the living space. Never run the boiler without an installed venting system. Carbon monoxide detectors should be installed and maintained in line with local rules.
- Check that the venting system is installed and connected before operating the boiler.
- Check that vents and chimneys are not blocked or partly blocked.
- Check for moisture, water or rust on flue pipes, joints, dampers and side wall terminals.
- Confirm that carbon monoxide detectors are installed as local regulations require.
- Follow the installation instructions for mechanical room and venting requirements.
Carbon monoxide detector and gas vent signage (Massachusetts)
Viessmann · Vitodens 200-W B2HA 19, 28, 35 on Massachusetts installations
Applies to side-wall horizontally vented gas equipment in residential buildings where the vent terminal is less than 7 ft above finished grade.
- Confirm a hard-wired CO detector with alarm and battery backup is installed on the floor level where the boiler is located.
- Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level served.
- If the boiler is in a crawl space or attic, the hard-wired detector may be on the next adjacent floor level.
- If the requirement cannot be met at completion, the owner has 30 days. A battery-operated CO detector with alarm must be installed in the meantime.
- Use CO detectors that meet NFPA 720, are ANSI/UL 2034 listed and IAS certified.
- Mount a metal or plastic sign on the building exterior at least 8 ft above grade, directly in line with the vent terminal. Lettering must be at least 1/2 in. and must state the gas vent is directly below and to keep the area clear of obstructions.
- Note that the state or local gas inspector will not approve the installation without the detectors and sign.
Carbon monoxide detector and signage for low side-wall vents (Massachusetts)
Viessmann · Side-wall horizontally vented installs in Massachusetts
For side-wall horizontally vented gas equipment in dwellings where the vent termination is under 7 ft above grade, Massachusetts rules apply. Hard-wired CO detectors with battery backup go on the floor level of the install and battery or hard-wired detectors on each additional level. A sign is required 8 ft above grade in line with the vent.
- Install a hard-wired CO detector with battery backup on the floor level where the gas equipment is installed.
- Install a battery or hard-wired CO detector with alarm on each additional level served.
- Mount the metal or plastic sign at least 8 ft above grade, directly in line with the vent terminal, reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS, with letters at least 1/2 inch.
Carbon monoxide detector and signage requirements (Massachusetts)
Viessmann · Side-wall horizontally vented installations in Massachusetts
For side-wall horizontally vented installations in Massachusetts, a hard-wired CO detector with battery backup must be on the floor level where the gas equipment is installed, and detectors must be on each additional level. Signage is also required. Exemptions apply to certain equipment and to units in a separate structure.
- Confirm a hard-wired CO detector with alarm and battery backup is installed on the equipment's floor level.
- Confirm a battery or hard-wired CO detector is installed on each additional level.
- Confirm the required metal or plastic sign is mounted at least 8 ft above grade in line with the vent terminal.
Carbon monoxide detector and signage rules for Massachusetts side-wall venting
Viessmann · Massachusetts side-wall horizontal venting with exhaust under 7 ft
For side-wall horizontal venting where the exhaust termination is under 7 ft above grade, Massachusetts rules require hard-wired CO detectors with battery backup on each level and a warning sign at the vent. The sign must be at least 8 ft above grade, in line with the vent.
- Install a hard-wired CO detector with alarm and battery backup on the floor level where the gas equipment is located.
- Install a battery-operated or hard-wired CO detector on each additional level served.
- Mount a metal or plastic sign reading "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS" at least 8 ft above grade, in line with the vent.
Carbon monoxide detector requirement (Massachusetts)
Viessmann · Installations in the Commonwealth of Massachusetts
For side-wall horizontally vented gas equipment with the vent termination under 7 ft above grade, Massachusetts rules require CO detectors with alarm and battery backup on the floor where the appliance is installed, plus detectors on each additional level. A metal or plastic sign reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS must be mounted at least 8 ft above grade in line with the vent terminal. If the detector cannot be installed at completion, a battery detector is required for 30 days.
Carbon monoxide detectors
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
The U.S. Consumer Product Safety Commission recommends CO detectors in buildings with gas-burning equipment. Installers must follow local rules.
- Install carbon monoxide detectors that meet a recognized standard (e.g. ANSI/UL 2034, CSA 6.19-01) where local rules require them.
- Maintain the detectors.
- Make sure the installation and service of the boiler are done properly to avoid carbon monoxide formation.
Carbon monoxide detectors and venting
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Improper installation, adjustment, service or maintenance can let flue gas into living space. The boiler must never run without an installed venting system.
- Never run the boiler without the venting system connected.
- Follow local rules for installing carbon monoxide detectors.
- In Massachusetts, sidewall-vented gas equipment with the vent less than 7 ft above grade needs hard-wired CO detectors with battery backup on the floor where the gas equipment is installed, and a warning sign 8 ft above grade in line with the vent terminal. The sign must read "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
Carbon monoxide detectors in Massachusetts
Viessmann · Side-wall horizontally vented installations in Massachusetts
For side-wall horizontally vented gas equipment in Massachusetts where the vent termination is less than 7 feet above grade, a hard-wired CO detector with alarm and battery backup is required on the floor level of the equipment, plus detectors on each additional level. A warning sign must be placed on the exterior 8 feet above grade in line with the vent.
- Confirm hard-wired CO detectors with battery backup are installed on the equipment floor level.
- Confirm battery or hard-wired CO detectors are installed on each additional level.
- Confirm the exterior sign reads "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS" at 8 feet above grade.
Cascade addressing for GW6B and MW2C controls
Viessmann · Vitotronic 300 GW6B cascade, Vitotronic 300-K MW2C (Vitodens 200, B2HA)
Cascade controls must use fixed LON addresses so the gateway can find every boiler.
- On Vitotronic 300 GW6B used as master cascade control, set the control to LON address 1 at coding address 77 for the master or lead boiler.
- Set the following boilers to LON addresses 2 to 8.
- For Vitotronic 300-K MW2C (Vitodens B2HA), set AO2 Cascade Config to 1 so the cascade is at address 9.
- Set the MW2C to LON address 77 with a value of 9, so the boilers run from LON address 1 to 8.
- If boiler communication uses KMK instead of LON, set AO3 Comm Config to 1.
Cascade adjustment strategies
Viessmann · Versatronik 300 cascade control
Pure modulation staging: raise Stage On (up to about 10C/18F or 15C/27F) so boilers are not forced on by temperature. Set Maximum Burner Mod to the point where the next boiler should start; each boiler then comes on at that value. To stage off sooner, set Minimum Burner Mod above the 30% default. Temperature dependent: keep Stage On at factory default or lower it so boilers are brought on faster. Each boiler still modulates to its own set point.
Cascade control unit roles
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Control unit A runs as the system and lead boiler section 1 control, with the cascade role shown as 'Lead boiler + cascade'. Control units B and C run as lag boiler section controls. Unit C applies to 5.0 and 6.0 models only.
- Identify the control units: A = system and lead boiler section 1, B = boiler section 2, C = boiler section 3 (5.0 and 6.0 only).
- Use the fuel selector switch D as needed for the fuel in use.
Cascade default display
Viessmann · Vitocrossal 200 CI2 cascade systems
Cascade displays show all cascade participants, the current supply temperature and target supply temperature. The lead boiler is marked with a star. Each participant's status and burner run hours can be viewed. Emissions test mode can be run only on a lag appliance. Dynamic control strategy is described elsewhere in the manual.
- Check the star to confirm which boiler is the lead appliance.
- Open a participant to see its status and burner run hours.
- Use the all-on function only to switch on standby-deactivated displays of cascade participants.
- Run emissions test mode only on a lag appliance.
Category I vent installation practices
Viessmann · Vitorond 200 VD2A boiler, Category I
Category I venting is for natural gas or LP and must use approved vent material. The boiler must not connect to any mechanical draft system under positive pressure. Keep the vent run short with few elbows and avoid long horizontal runs. Correct any downdraft or condensation problems.
- Locate the boiler as close to the chimney as possible and use the shortest vent path with minimal elbows.
- Rearrange existing water piping if needed to shorten the vent connection.
- Support horizontal runs to prevent sagging and check the rise per the venting dimensions.
- Drill a 1/2 in. (13 mm) test opening on the side of the vent pipe about three vent diameters from the flue collar for combustion analysis.
- Where the boiler vents into a masonry or unlined chimney, install an approved stainless steel liner.
- Observe local codes for any vent into a chimney or breeching shared with a direct-fired gas water heater.
Category III positive pressure venting
Viessmann · Vitorond 200 boiler, Category III
The Vitorond 200 is a Category III positive pressure non-condensing boiler and must be vented individually. The vent must be gas tight and use a suitable stainless steel system listed for Category III.
- Use an AL29-4C special stainless steel venting system listed for Category III for single-wall vertical venting.
- Connect the flue outlet with the shortest run, a slight upward slope to the stack, and no sharp bends. Flue outlet outside diameter is 8 in. (200 mm).
- Drill a 10 mm test hole in the side of the vent pipe about two to three vent diameters from the flue collar.
- Seal and insulate the vent pipe.
- Follow the Viessmann positive pressure venting system instructions for details.
Central control of heating circuits (coding 7a)
Viessmann · Multiple heating circuits
Coding 7a in the General group sets central control to one heating circuit. Its operating and holiday program then applies to all other heating circuits.
- When the central operating and holiday program is enabled, 'Central control' is shown on the other heating circuits.
- Any holiday programs previously set on those circuits are deleted.
- Party and economy modes are not available on all control units.
Central heating without DHW heating
Viessmann · Vitotronic 300-K MW1B
No program exists for central heating alone. Hot water is normally also required in winter.
- Select the heating program Heating and DHW
- Set the DHW temperature to 50 F (10 C) so DHW is not heated unnecessarily, while DHW tank frost protection is kept
Centralized operation display
Viessmann · Vitotronic 200-H HK1S/HK3S
If centralized operation is coded on a boiler and heating circuit or cascade control, the heating and holiday program settings are accepted from the central unit.
Change or delete a time phase
Viessmann · Time programs
Edit the start point of an existing time phase, or remove a phase from one day.
- Select the heating circuit and the day.
- Select the time phase with the arrow.
- To change the start, set the new time and the temperature level, then confirm.
- To delete, use the X and confirm.
- Exit the time program.
Change the central heating time program
Viessmann · Central heating time program
Set the on and off times for up to four central heating phases, either the same for all days or separately for each weekday.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button until it lights up.
- Press the time program button until 'Central heating time program' shows in the display.
- Choose '1-7' for the same phases every day, or a weekday (Mo, Tu, etc.) for individual days, then confirm.
- Set the phase 1 ON time, then confirm, then set the phase 1 OFF time, then confirm.
- Repeat for phases 2 to 4. Skip a phase by pressing the skip button.
- Close the hinged cover. After the finishing time of phase 4 is confirmed, the display shows the boiler sequence.
Check active messages by type
Viessmann · Vitodens 100-W B1HE/B1KE
Lists are shown by type: Burner faults, Faults, Warnings, Maintenance, Status and Information. Only types with current messages are listed.
- Call up the home screen and open the menu.
- Select Active messages, then tap OK.
- Select the required message type, then tap OK.
- Select the required message, then tap OK.
- Read the message details.
- Hold the exit button for about 4 seconds to leave the menu.
Check and acknowledge service messages
Viessmann · Service messages menu
Service messages are listed in yellow. If the service cannot be done yet, the message appears again the following Monday. When the contractor's service interval is exceeded, a 'Service' message appears automatically. The contractor's contact details show if available.
- Tap the navigation area.
- If fault messages are present, open 'Faults', then 'Service messages'.
- Tap a message to see details and self-help tips.
- Write down the service message number and notify your contractor.
- Acknowledge the service if needed.
Check and replace refractory ring and DHW tank burner
Viessmann · Vitodens 200-W B2HA
Inspect the burner refractory ring and the DHW tank burner assembly for damage and replace if needed. Use a calibrated torque wrench for the fasteners.
- Remove the electrode block and ionization electrode.
- Release the three retaining clips on the refractory ring and remove the ring.
- Remove the four Torx screws, then the DHW tank burner assembly and its assembly gasket.
- Fit the new DHW tank burner assembly and new gasket. Tighten to 3.3 lb.ft (4.5 Nm).
- Refit the refractory ring and secure with the retaining clips.
- Refit the electrode block and ionization electrode. Tighten to 3 lb.ft (4 Nm).
Check communication with the boiler
Viessmann · Versatronik COMO OT
When the communication symbol shows on the display, data exchange with the boiler is working. If it is not shown next to the clock, the boiler data cable is faulty or disconnected.
- Look for the communication symbol next to the clock.
- If it is absent, check the data cable to the boiler.
Check controls and wiring before troubleshooting
Viessmann · Vitotronic 100 KW10B boiler systems
Before troubleshooting any fault, confirm the system controls work and the wiring is sound.
- Check that all controls operate properly, such as thermostats and the low water cut-off.
- Check that all wire connections are tight and secure.
Check estimated energy consumption
Viessmann · Energy metering
The value is calculated and may differ from actual consumption. It is not suitable for billing.
- Call up the home screen.
- Select Energy metering, then confirm with OK.
- Select Consumption, then confirm with OK.
- Select the current month or last month, then confirm with OK.
- Read off the value.
- Press and hold the exit button for about 4 sec to leave the menu.
Check heating circuit allocation
Viessmann · Vitotronic 200-H programming unit
Confirm the heating circuit allocation label is on the matching array of the programming unit before making changes.
- Check that the heating circuit allocation label is affixed to the correct array on the programming unit.
- Select the corresponding heating circuit before adjusting any settings.
Check heating zone status on a lead or lag boiler
Viessmann · Cascade systems
Shows the status of heating zones from a cascade lead or lag boiler.
- Select the device status of the lead or lag boiler.
- On the lead boiler, tap the symbol in the middle of the screen.
- Read the heating zone status.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.