Viessmann Boiler: Cascade addressing for GW6B and MW2C controls

Updated · by Aurora Star Tech Inc.

Cascade addressing for GW6B and MW2C controls on a Viessmann boiler: Cascade controls must use fixed LON addresses so the gateway can find every boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300 GW6B cascade, Vitotronic 300-K MW2C (Vitodens 200, B2HA)

How to fix cascade addressing for gw6b and mw2c controls: step by step

  1. On Vitotronic 300 GW6B used as master cascade control, set the control to LON address 1 at coding address 77 for the master or lead boiler.
  2. Set the following boilers to LON addresses 2 to 8.
  3. For Vitotronic 300-K MW2C (Vitodens B2HA), set AO2 Cascade Config to 1 so the cascade is at address 9.
  4. Set the MW2C to LON address 77 with a value of 9, so the boilers run from LON address 1 to 8.
  5. If boiler communication uses KMK instead of LON, set AO3 Comm Config to 1.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Versatronik 585 VI/BACIP

More other tips for boiler

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 15. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.