Viessmann Boiler: Carbon monoxide detector and signage for low side-wall vents (Massachusetts)
Carbon monoxide detector and signage for low side-wall vents (Massachusetts) on a Viessmann boiler: For side-wall horizontally vented gas equipment in dwellings where the vent termination is under 7 ft above grade, Massachusetts rules apply. Hard-wired CO detectors with battery backup go on the floor level of the install and battery or hard-wired detectors on each additional level. A sign is required 8 ft above grade in line with the vent.
Applies to: Side-wall horizontally vented installs in Massachusetts
How to fix carbon monoxide detector and signage for low side-wall vents (massachusetts): step by step
- Install a hard-wired CO detector with battery backup on the floor level where the gas equipment is installed.
- Install a battery or hard-wired CO detector with alarm on each additional level served.
- Mount the metal or plastic sign at least 8 ft above grade, directly in line with the vent terminal, reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS, with letters at least 1/2 inch.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.