Viessmann Boiler: Bypass required on large water content systems
Bypass required on large water content systems on a Viessmann boiler: Systems with more than 1 USG of water for every 13,000 Btu/h of boiler input (for example, older gravity systems with large free-standing radiators) need a supply-to-return bypass to prevent flue gas condensation in the heat exchanger and vent. Viessmann recommends a bypass on all cast iron boilers.
Applies to: Vitorond 100 VR1 boilers on large water content systems
How to fix bypass required on large water content systems: step by step
- Calculate system water volume against boiler input (1 USG per 13,000 Btu/h).
- If the system is above that ratio, install a bypass pipe from the supply pipe to the return pipe.
- Install the bypass on any system as a precaution if preferred.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitorond 100 VR1 installation and service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.