Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Commissioning: Boiler tips (part 5 of 21)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Assign a heating circuit to the remote control (key method during operation)

Viessmann · Vitotrol 200A remote control

Changes the heating circuit assignment while the system is running.

  1. Press the two keys shown on the remote control together for about 4 seconds.
  2. Use the +/- keys to select heating circuit 1 (H 1), 2 (H 2) or 3 (H 3).
  3. Press OK to confirm. The operating state of the heating system is transferred.
  4. Wait for the display segments to finish rotating (this can take up to 5 minutes).

Assign a heating circuit to the remote control (power-up method)

Viessmann · Vitotrol 200A remote control

Used when the remote control is first connected to the boiler control unit. Up to 2 remote controls can be connected to one control unit.

  1. Switch on the power supply at the control unit. The remote control shows H 1.
  2. Use the +/- keys to select heating circuit 1 (H 1), heating circuit 2 (H 2) or heating circuit 3 (H 3).
  3. Press OK to confirm. The operating state of the heating system is transferred.
  4. Wait for the display segments to finish rotating (this can take up to 5 minutes).

Assign functions in the commissioning assistant

Viessmann · P1, P2, lH and tank sensor

Relay and input functions are chosen in the commissioning assistant by selecting the connected component.

  1. Open the commissioning assistant.
  2. Select the connected component for P1, P2, lH or the tank sensor.

Autobinding reset without a power cycle

Viessmann · Versatronik 503 rotary dial S1

Use this when the LON participant number has to change without a power cycle, or when a tool binding must be cleared.

  1. Set the S1 dial to position 9.
  2. Wait 10 seconds.
  3. Press and hold the service button for 2 seconds.
  4. Wait 10 seconds.
  5. Set the dial to the desired boiler number.
  6. Wait about 10 seconds for the new address to take effect.

Automatic summer and winter time changeover

Viessmann · Controllers in Central European time zones

The controller changes time automatically on the Sunday after the set start date, at 2:00 or 3:00 am. Only change the default if the rule changes.

  1. Set the earliest date for the change under the summer time start and end entries.
  2. Leave the default unless the date is changed by political decree.

Avoid overheating the heat source with dynamic settings

Viessmann · Versatronik 200 modulating boilers

Stage-on and stage-off dynamic values that are too low or too high can overheat the heat source and trip the STB.

  1. Keep Stage-on dynamic and Stage-off dynamic within 20-500 K.
  2. Check the STB (safety thermal cutout) after changing these values.
  3. Do not set values too low or too high for the system load.

Balancing valve placement

Viessmann · Vitorond 200 VD2 boilers

Valve position is needed for laminar flow through the boiler.

  1. Install any balancing valve 5 pipe diameters from fittings.
  2. Install any balancing valve 10 pipe diameters from circulation pumps.
  3. Have a certified balancing firm balance the system before boiler start-up.

Balancing valve placement and balancing

Viessmann · Vitorond 200 VD2A hydronic piping

Balancing valves must be placed with enough straight pipe for laminar flow. The balancing must be done by a certified balancing firm before boiler start-up.

  1. Install the balancing valve 5 pipe diameters from any fittings.
  2. Install the balancing valve 10 pipe diameters from circulation pumps.
  3. Have a certified balancing firm balance the system before start-up.
  4. Ask the consulting engineer to review the design if more balancing valves are needed.

Barometric draft regulator type and location

Viessmann · Vitorond 200 VD2 boilers

A barometric draft regulator is required in the chimney or vent for proper operation.

  1. For natural gas or propane, use a double-acting barometric draft regulator.
  2. For #2 fuel oil, use a single-acting barometric draft regulator.
  3. Install the regulator 5 to 7 ft. (1½ to 2 m) from the breeching outlet at the rear of the boiler.
  4. Size the regulator opening to match the chimney diameter, not the breeching outlet.

Beckett GeniSys post purge

Viessmann · Beckett NX burner with GeniSys control

The GeniSys control has post purge set at the factory.

  1. Factory default post purge is 30 seconds.
  2. Field adjustment is allowed. Follow the Beckett burner manual.

Boiler circuit pump sizing for cascade systems

Viessmann · Multi-boiler systems with boiler circuit pumps (system versions 4 to 5)

Each boiler circuit pump must move at least the total heating circuit volume flow. Recommended margin is 110%.

  1. Size each boiler circuit pump for at least the maximum total heating circuit volume flow.
  2. Apply the recommended 110% margin.

Boiler coding card

Viessmann · Vitotronic 300 KW3

Only the coding card supplied with the boiler may be used. It comes in the boiler accessory pack.

  1. Push the boiler coding card through the recess in the cover.
  2. Insert it in plug-in location X7.

Boiler connection kit contents

Viessmann · Vitorond 200 VD2A boiler connection kit

The standard boiler connection kit includes a safety supply connection to the pressure relief valve, a low water cut-off, a temperature gauge and the boiler water supply connection. A single or dual aquastat is optional.

  1. Connect the safety supply to the pressure relief valve.
  2. Install the low water cut-off in its connection.
  3. Install the temperature gauge in its connection.

Boiler in heating/cooling application valve setup

Viessmann · Vitodens 100-W WB1B with refrigeration system or chiller

When the chilled medium is piped in parallel with the boiler, valves stop chilled water from entering the boiler. Flow control valves or automatic means are needed to prevent gravity circulation during cooling.

  1. Label the valves v1 and v2.
  2. Cooling season: close valve v1 and open valve v2.
  3. Heating season: close valve v2 and open valve v1.
  4. Check the chiller manufacturer's installation instructions for extra requirements.

Boiler piping with a chiller (heating/cooling)

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler through valves so chilled medium cannot enter the boiler. Hot water coils in air handlers exposed to refrigerated air need flow control valves or another automatic means to stop gravity circulation during cooling.

  1. Pipe the chilled medium in parallel with the boiler using valves.
  2. Add flow control valves or an automatic means on hot water coils in air handlers exposed to refrigerated air.
  3. Use a spring-loaded flow check valve and a safety header with automatic air vent and pressure relief valve as shown.
  4. Check the chiller manufacturer's installation instructions for additional requirements.

Boiler placement and levelling

Viessmann · Vitorond 100 VR1 boilers

Place the boiler close to the chimney and protect the oil ignition components from water spray or splashing during operation and service.

  1. Locate the boiler as close to the chimney as possible.
  2. Set the boiler with a slight incline toward the rear using the levelling bolts.
  3. Protect oil ignition system components from water spraying or splashing.

Boiler sensor installation

Viessmann · Vitotronic 100 KW10B

The boiler sensor goes into the boiler sensor well. Do not kink the surrounding capillaries.

  1. Insert the boiler sensor into the boiler sensor well without kinking the capillaries.
  2. Route the cable to the boiler control between the enclosure panels and insulation jacket.
  3. Connect the boiler sensor wires to connector X6 terminals 3.1 and 3.2.

Boiler water temperature limit

Viessmann · Vitotronic and high limit settings

Factory high limit is 167 °F (75 °C) on Vitotronic controls. The adjustable high limit can be raised to increase supply temperature. For new systems, Viessmann recommends designing radiation and DHW for 158 °F (70 °C) supply to reduce piping losses.

Boiler water temperature limit and supply design

Viessmann · Vitorond 200 VD2 boilers

The factory high limit is set at 167°F (75°C). Viessmann recommends designing for 158°F (70°C) to reduce piping losses.

  1. Leave the high limit at 167°F (75°C) unless the system needs more.
  2. Raise the adjustable high limit only if a higher supply temperature is required.
  3. Design radiation and domestic hot water for a 158°F (70°C) supply temperature where possible.

Burner blast tube and insulation fit-up

Viessmann · Vitorond 200 VD2A burner installation

Set the burner blast tube depth and seal the gap at the combustion chamber door.

  1. Make sure the burner blast tube projects at least 4.5 in. (110 mm) into the boiler from the front edge of the burner plate.
  2. After the burner is installed, fill the gap between the blast tube and the door insulation insert with the supplied insulating material.
  3. Seal the sight glass for pressure tightness.
  4. Connect the sight glass to the burner with the supplied clear plastic hose.

Burner primary control 120VAC supply

Viessmann · Beckett GeniSys and Carlin 70200 primary controls

The Beckett GeniSys or Carlin 70200 primary control needs a constant 120VAC supply on its black wire, even when the burner is idle.

  1. Connect a constant 120VAC supply to the BLACK wire on the primary control.
  2. Disconnect power before servicing the control.

Burner selection and firing pressure

Viessmann · Vitorond 200 VD2A burners

The burner must be ordered for a specific fuel or as a combination burner, and the boiler must run with positive pressure in the combustion chamber.

  1. Order the burner for the specific fuel, or as a combination burner naming the fuels.
  2. Use only an approved oil or gas burner type.
  3. Check the separate burner selection chart in the Technical Data Manual.
  4. Keep all components protected from water during operation and service.

Burner sight glass and door insulation

Viessmann · VD2-320 to VD2-1080

Seal the sight glass and avoid overtightening it. Fill the gap between the burner blast tube and the door insulation.

  1. Connect the sight glass to the burner with the clear plastic hose supplied.
  2. Seal the sight glass for pressure tightness.
  3. Do not overtighten the brass sight glass holder, as this can break the glass.
  4. After burner installation, fill the gap between the blast tube and the combustion chamber door insulation with the supplied insulating material.

BUS ID numbering for heating circuits

Viessmann · Versatronik 200 System Control

Heating circuits are numbered in order starting at 01, and no number may be used twice. If you replace a controller, enter exactly the same heating circuit numbers as the old controller.

  1. Number heating circuits in sequence from 01.
  2. Do not assign the same circuit number twice.
  3. On a replacement controller, enter the same heating circuit numbers as the unit being replaced.

Bus termination and Time Master checks

Viessmann · Versatronik 200 system with multiple controllers and bus

Only one bus termination resistor and only one Time Master may be used in the system. Incorrect settings can cause malfunctions.

  1. Confirm only one controller (HG or cascade controller) has BUS Termination set to On. Set it to Off if a CoCo is installed.
  2. Confirm only one controller has Time Master set to On.
  3. Check that heating circuit numbers (BUS ID) are unique; replacement controllers must match the old numbers.

Bypass required on large water content systems

Viessmann · Vitorond 100 VR1 boilers on large water content systems

Systems with more than 1 USG of water for every 13,000 Btu/h of boiler input (for example, older gravity systems with large free-standing radiators) need a supply-to-return bypass to prevent flue gas condensation in the heat exchanger and vent. Viessmann recommends a bypass on all cast iron boilers.

  1. Calculate system water volume against boiler input (1 USG per 13,000 Btu/h).
  2. If the system is above that ratio, install a bypass pipe from the supply pipe to the return pipe.
  3. Install the bypass on any system as a precaution if preferred.

Cable routing at the control unit

Viessmann · Vitodens 200-W B2HA 45, 60 control connections

Cables must be routed as illustrated so the control unit can move freely. Cables near the control unit must not be secured to the control unit bracket. Cable temperature ratings must not be exceeded.

  1. Route all cables as shown in the illustration.
  2. Do not secure cables to the control unit bracket.
  3. Check that the cable temperature ratings are not exceeded when routing and securing cables on site.

Carbon monoxide alarm and start-up paperwork

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Before the boiler is put into operation, confirm that at least one CO alarm is installed in the living space, following the alarm maker's instructions and local codes. The licensed heating contractor must complete the Maintenance Record at initial start-up.

Carbon monoxide alarm before operation

Viessmann · Vitocrossal 200 CI2

Installation requirement for CO protection.

  1. Confirm at least one carbon monoxide alarm is installed in the living space before the appliance is put into operation.
  2. Install, maintain and replace alarms per the alarm manufacturer's instructions and local codes.

Carbon monoxide alarm check

Viessmann · All B2HA models

Confirm at least one carbon monoxide alarm is installed in the living space before the boiler is put into operation, following the alarm maker's instructions and local codes.

  1. Verify a CO alarm is installed in the residence or living space.
  2. Only then start the appliance.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977