Viessmann Boiler: Burner control unit component key
Burner control unit component key on a Viessmann boiler: Key components on the burner control unit connection diagram that are used when troubleshooting burner fault codes.
Applies to: Vitocrossal 300 CA3B Dual Fuel
How to fix burner control unit component key: step by step
- Gas pressure switch at first valve seat: check when F6 or E1/E2 is shown.
- Gas valves V1 and V2: check connecting cable and replace if the fault points to the gas valve.
- Inlet fan pressure switch (APS1) and overfire pressure switch (APS2): check when F5 or F7 is shown.
- Fan motor with PWM control: check when F9, Fa or varying fan speed is shown.
- Ignition unit and flame sensor: check when F4 is shown.
- Burner damper servomotor: check when F3 poor start-up is shown.
- Vitotronic control unit: check the KM BUS connection when F0 is shown.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 131. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.