Other: Boiler tips (part 8 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Breech draft check
Viessmann · All VR1 sizes
Required flue draft is -0.02 in w.c. Draft at the breech is typically between -0.02 and -0.08 in w.c. Use a sized chimney that meets local and national codes wherever possible.
Brief scan of temperatures, software and connected parts
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Shows temperatures, software versions and connected components on a 9-line by 6-field display.
- Open the service level.
- Select Diagnosis, then Brief scan.
- Press OK. The display shows 9 lines with 6 fields each.
Built-in battery disposal
Viessmann · Vitotronic 200-H HK1S/HK3S
The control unit has a built-in non-toxic battery. A competent person should remove it. Dispose of depleted batteries at a proper collection point.
- Have a competent person remove the battery.
- Dispose of the battery at an appropriate collection point.
Built-in frost protection thresholds
Viessmann · Vitodens 100-W B1HE and B1KE
Frost protection is always active. The burner fires when boiler water reaches 41°F (5°C) and shuts off again once water reaches at least 59°F (15°C), but no more than 68°F (20°C).
Burner connection
Viessmann · Vitotronic 100 KW10B
The RAST-5 plug goes to the control PCB and the 7-pole plug goes to the burner or wall vent system counter plug. Do not connect the 41-plug from the boiler control directly to the burner when installing a wall vent system.
- Connect the RAST-5 plug to the main control circuit board.
- Connect the 7-pole plug to the burner counter plug, or to the wall vent system counter plug if one is installed.
- Do not connect the 41-plug directly to the burner when a wall vent system is used.
Burner control display layout and exit
Viessmann · Vitocrossal 200 CM2 burner control unit
The four-digit display has a status display and a service display, plus LEDs for heat demand, flame, maintenance and fault. Standard mode scrolls through the operating states. In a fault state the status display shows the current condition after pressing reset.
- Press and hold the reset button for more than 2 seconds to exit any display or menu.
Burner control terminals T6, T7, T8
Viessmann · Vitotronic 100 KW10B
Terminals T6, T7 and T8 carry the control signal for a two-stage burner or a modulating burner. Two-point control gives two-stage operation; three-point control gives modulating direction. Control to burner and burner to control signal directions are both marked on the terminal diagram.
- Confirm burner type (two-stage or modulating) before wiring T6, T7 and T8.
- Use the 2-stage/modulating burner extension as described in its installation instructions.
Burner control unit component key
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Key components on the burner control unit connection diagram that are used when troubleshooting burner fault codes.
- Gas pressure switch at first valve seat: check when F6 or E1/E2 is shown.
- Gas valves V1 and V2: check connecting cable and replace if the fault points to the gas valve.
- Inlet fan pressure switch (APS1) and overfire pressure switch (APS2): check when F5 or F7 is shown.
- Fan motor with PWM control: check when F9, Fa or varying fan speed is shown.
- Ignition unit and flame sensor: check when F4 is shown.
- Burner damper servomotor: check when F3 poor start-up is shown.
- Vitotronic control unit: check the KM BUS connection when F0 is shown.
Burner control unit display and buttons
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
Each burner control unit has an integrated display with a status display (A), a service display (B), reset button (C/R), LEDs (D: heat demand, flame, maintenance, fault), a selection button (F) and cursor buttons (E/G). In normal mode the status display shows the current operating condition, and after reset it shows the fault condition. Faults are shown with fault codes.
- Read the status display for the current operating condition.
- After a fault, press reset R to see the fault condition.
- Hold reset R for 0.5 to 10 seconds to exit the current display.
Burner fault codes are in the burner section
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Burner faults show on the control unit display, but the burner fault code list is not on these pages. Use the burner section of the manual, which starts on page 53.
- Refer to the burner section starting on page 53 for burner fault codes.
Burner fault codes are serviced in the burner section
Viessmann · Burner fault codes F0 to Fd
Burner fault codes are shown on the control unit display. Service the burner using the burner section of the manual.
- Read the burner fault code on the control unit display.
- Refer to the burner section starting on page 53 to service the burner.
Burner head material temperature rating
Viessmann · All VD2 models 320 to 1080
The combustion burner head material must be rated for at least 932°F (500°C).
- Check that the burner head material is rated for at least 932°F (500°C).
Burner installation and fuel selection
Viessmann · Vitorond 200 VD2A boiler
Only approved oil or gas burners may be used. Order the burner for a specific fuel or as a combination burner. The combustion chamber must run under positive pressure. Keep all burner components protected from water.
- Confirm the burner is ordered for the correct fuel: #2 fuel oil or natural gas or LP.
- Make sure the blast tube protrudes at least 4.5 in. (110 mm) into the boiler from the front edge of the burner plate.
- Fill the gap between the blast tube and the insulation insert on the combustion chamber door with the supplied insulating material.
- Seal the sight glass for pressure tightness.
- Connect the sight glass to the burner with the supplied clear plastic hose.
- Protect the boiler and burner from dripping, spraying and rain during operation and service.
Burner modulation percentage is approximate
Viessmann · Versatronik 501 gateway modulation status
The nvoBStatus value gives modulation in percent for boilers 1 to 4 (one byte each). It is only a control approximation and does not show the true burner position. Check the burner manufacturer documentation for actual position.
Burner mounting and door insulation
Viessmann · All VD2 models 320 to 1080
The burner must be fitted to the burner plate. Direct mounting to the boiler door is not allowed. Viessmann supplies a pre-drilled end burner plate that matches the supplied burner dimensions. For blast tube diameters of 7 to 11 in. (180 to 280 mm) the door refractory can be cut to size. The blast tube must extend past the thermal insulation on the boiler door.
- Fit the burner to the pre-drilled burner plate, not to the boiler door.
- For blast tubes 7 to 11 in. (180 to 280 mm), cut the door refractory to the required size.
- Make sure the blast tube protrudes past the door insulation.
Burner mounting on the burner plate
Viessmann · Vitorond 200 VD2A burner installation
The burner must be mounted to the burner plate, not directly to the boiler door. The blast tube must protrude through the door insulation.
- Mount the burner to the supplied pre-drilled end burner plate.
- For blast tubes over 6 in (150 mm), cut the door refractory insulation to size.
- Confirm the blast tube protrudes from the door insulation.
Burner terminal reference
Viessmann · Vitotronic 300 KW3
Terminal codes on the burner connection: L1 is line via safety high limit, PE is ground, N is neutral, T1 and T2 are the control circuit, S3 is the burner fault input, and B4 is the operating hours counter input.
Burner wiring: follow the burner maker's drawing
Viessmann · Any burner connected to the Vitotronic
The burner connection drawing in the manual is generic. Use the burner manufacturer's Viessmann control drawings for the real wiring, and mark the terminal numbers on the drawing for future reference.
- Get the burner manufacturer's connection drawing for Viessmann controls.
- Mark the terminal numbers or markings on the drawing.
- Keep the burner power supply in mind, since it is not shown on the generic drawing.
Cable routing near the boiler
Viessmann · Control unit wiring
Keep control and sensor wiring away from heat.
- Route cables through the boiler front panel into the control wiring chamber.
- Never let cables touch hot metal components.
- Secure the cables to the top rail with cable ties and route through the cable retainers.
Cable strain relief at the control unit
Viessmann · Vitotronic 100 GC1 installation
Cables run from the connection enclosure into the control unit and need strain relief.
- Run the cables from the connection enclosure into the control unit.
- For cables with moulded strain relief, connect the cable and the strain relief clamp.
- Otherwise, fasten the cable to the cable lead with a cable tie.
Call up acknowledged fault messages
Viessmann · Vitocrossal 200 CI2 boilers
Lists earlier fault messages that were acknowledged but may still be relevant. They appear in time order.
- Open the main menu.
- Tap "Message lists".
- Review the fault list in chronological order.
Call up active fault messages
Viessmann · Vitocrossal 200 CI2 boilers
When a fault is present the display shows the fault message. If a central fault facility is connected it is also started.
- Tap the fault button in the footer to show the fault messages.
- Read the fault code and look it up in the fault table.
- Tap to hide the fault messages when finished.
Call up fault history
Viessmann · Vitodens 200-W B2HA 45, 60
The last 10 faults, including resolved ones, are stored and sorted by date.
- Enter the service level (OK and the second key for about 4 seconds).
- Select Fault history.
- Select Display? and review the fault codes.
Call up help messages
Viessmann · Control panel
Help messages explain the displays and functions.
- Tap the help icon to show help messages.
- Tap the back icon to return to the previous screen.
Calling up and acknowledging fault messages
Viessmann · Heating system
Fault messages appear in red. Acknowledging stops the signal device. Faults that cannot be fixed now return the next day and the alarm is switched back on.
- Tap the fault symbol in the footer. The fault list appears.
- Tap a fault to see its information and self-help tips.
- Note the fault code and cause. Example code shown: f0 Combustion controller.
- Tap Close, then notify the heating contractor.
Calling up and confirming service messages
Viessmann · Heating system
Service messages appear in orange. If a service cannot be done yet, the message returns the following Monday until the heating contractor resets the interval.
- Tap Confirm. The footer shows the service symbol.
- Tap the service symbol in the footer to show the list.
- Notify the local heating contractor.
CAN bus subscriber numbers and electronics modules
Viessmann · Vitodens 100-W B1HE/B1KE
When troubleshooting, note the subscriber number shown with the fault and check that component. Modules: A = BCU burner control unit, B = HMU heat management unit with wiring panel, C = HMI programming unit with WiFi module.
- Subscriber 1: HMU heat management unit.
- Subscriber 50: BCU burner control unit.
- Subscriber 58: communication module (TCU 200).
- Subscriber 59: HMI programming unit.
- Subscriber 60: fan unit.
- To find the module, check the rotary switch S1 on the module if needed.
Capability expansions available with Vitotronic 200 and 300
Viessmann · Switching Module-V
Supported functions: remote burner disable, external heat demand, external heat demand (2nd stage with two-stage burners), remote switching of operating mode to continuous reduced operation and back, short-term DHW recirculation pump operation, external fault input, and connection of a compiled fault indicator.
Capillary handling warning (CM2)
Viessmann · CM2 control installation
Damaged capillaries cause control malfunction.
- Do not bend or kink the capillaries.
Carbon monoxide alarm before start-up
Viessmann · Vitocrossal 300 CU3A, all models
The installer must confirm that at least one carbon monoxide alarm is installed in the living space before the appliance is put into operation. Alarms must be installed, maintained and replaced per the alarm maker's instructions and local codes.
- Confirm at least one CO alarm is installed in the living space before commissioning.
- Follow the alarm manufacturer's instructions and local codes for installation and replacement.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.