Viessmann Boiler: Boiler will not reset after F2 fault shutdown

Updated · by Aurora Star Tech Inc.

Boiler will not reset after F2 fault shutdown on a Viessmann boiler: If the burner control unit will not reset after a fault shutdown (F2) even though boiler water is below about 203°F (95°C), check the fixed high limit switch.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Fault shutdown F2, fixed high limit

Common causes of boiler will not reset after f2 fault shutdown

  • Faulty fixed high limit switch

How to fix boiler will not reset after f2 fault shutdown: step by step

  1. Pull the leads from the fixed high limit.
  2. Check continuity of the fixed high limit with a multimeter.
  3. Remove a faulty fixed high limit.
  4. Coat the replacement fixed high limit with heat conducting paste and install it.
  5. Reset the control as described on page 76 of the manual.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

WB1AWB1B

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 80. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.