Viessmann Boiler: Boiler pump runs continuously after switching to multi-boiler operation

Updated · by Aurora Star Tech Inc.

Boiler pump runs continuously after switching to multi-boiler operation on a Viessmann boiler: In multi-boiler operation, coding address 30:0 can change to 30:3 on its own, which makes the boiler pump run continuously.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200 B2HA in multi-boiler systems

How to fix boiler pump runs continuously after switching to multi-boiler operation: step by step

  1. Verify that coding address 30:0 is set on each boiler.
  2. Set 30:0 if necessary (see page 59).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More other tips for boiler

Source: Vitodens 200-W B2HA service instructions, p. 84. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.