Other: Boiler tips (part 7 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Barometric draft regulator type and size
Viessmann · Vitorond 200 VD2A oil and gas boilers
Choose the regulator type by fuel. The regulator opening must match the chimney it serves, not the boiler breeching.
- On natural gas or propane, use a double-acting barometric draft regulator.
- On No. 2 fuel oil, use a single-acting barometric draft regulator.
- Size the regulator opening to the chimney diameter the vent is designed for.
- Do not size the regulator to the boiler breeching outlet unless the chimney is the same diameter.
Basic display shows boiler sequence
Viessmann · Vitocontrol-S, VD2/CT3/CM2
The default screen shows the boiler sequence and boiler temperature. It returns to this screen after each setting is entered.
- Confirm the basic display after a setting is entered.
- If the screen does not change, wait for it to time out to the boiler sequence view.
Basic display shows supply temperature
Viessmann · Vitotronic 200-H HK1S and HK3S
In the basic display the window shows the supply temperature in degrees C. A participant check message appears when no other control units are connected, or when several interconnected control units are installed.
Basic display shows the boiler sequence
Viessmann · Vitocontrol-S, VD2/CT3/CM2
In normal operation the Vitocontrol-S display shows the boiler sequence. It returns to that view after every setting you make.
- After you finish a setting, wait for the display to return to the boiler sequence view.
Before servicing: power and gas isolation
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Isolate all power and the gas supply before any service work to prevent accidental start-up.
- Turn off main power to the boiler, heating system and all external controls.
- Close the main gas supply valve.
- Keep precautions in place so power is not restored during work.
Blocked vent safety switch (Canada)
Viessmann · Vitorond 100 VR1 boilers sold in Canada
Canadian installations include a blocked vent safety switch in the vent connection. Install it per the instructions in the manual.
- Locate the blocked vent safety switch shown in the venting connection drawing.
- Install it according to the manual instructions before commissioning.
Board and module reference in wiring summary
Viessmann · Vitotronic 100 GC1 wiring
Reference list of the component IDs used in the connection and wiring diagrams: A2 low voltage motherboard, A3 line voltage motherboard, A6 programming unit, A7 Optolink PCB and override switch, A8 supplementary PCB, A9 boiler coding card, A10 LON communication module, A11 power supply PCB, A12 boiler control unit.
Boiler 3 data points readable via Versatronik 503 on a Vitogate 300
Viessmann · Vitogate 300 with GW6B lead control
The Vitogate 300 does not recognise the Versatronik 503 and cannot talk to the target boiler directly. It can still read some boiler 3 values through the cascade control, for example on a GW6B lead control.
- Read AI:1085 - 1.1 for boiler 3 output value.
- Read AI:1050 - 1.1 for boiler 3 water temperature.
- Read AI:1059 - 1.1 for boiler 3 set water temperature.
- Read MI:1033 - 1.1 for boiler 3 fault.
- Read MI:1013 - 1.1 for boiler 3 operating mode.
Boiler cleaning interval
Viessmann · Vitotronic 300-K MW1B / Vitotronic 100 GC1B
Boiler contamination raises flue gas temperature and energy losses.
- Clean all boilers annually
Boiler control and harness mounting
Viessmann · Vitorond 200 VD2A boiler
The control housing and burner harness bracket mount to the side panel. Capillaries and the boiler sensor must stay away from heat sources such as the vent, chimney and supply or return piping.
- Drill the four mounting holes on the side panel as shown (mirror the drawing for left-side mount) and punch the 7/8 in. (22 mm) opening.
- Install the control harness bracket with the supplied 8-32 self-tapping screws.
- Install the burner harness bracket with two supplied screws.
- Remove the two plugs on the back of the control housing and mount it on the side panel with two screws.
- Run capillaries and the boiler temperature sensor through the side opening and insert the sensor into the sensor well as far as possible.
- Install the top panels and the name plate.
- In Canada, install the oil door safety switch per its separate instructions.
- Follow the boiler control installation instructions for electrical connections.
Boiler controls the gateway supports
Viessmann · Versatronik 505 and 505D
The gateway is listed for the Vitocontrol-S, Vitotronic 300-K, 100, 300 (GW2, GW5B), 200 and Vitodens 200 B2HA controls. Each control has its own communication setup and connection detail.
Boiler exposed to water
Viessmann · All CM2 models
Do not run the boiler if any part was under or exposed to water.
- Do not use the boiler.
- Call a qualified heating contractor to inspect the boiler.
- Have the control system and any gas control that were exposed to water replaced.
Boiler has been under water
Viessmann · Vitocrossal 300 CU3A, all models
A boiler that has been flooded must not be used. The control system and any gas control that was under water must be replaced.
- Do not use the boiler.
- Call a qualified heating contractor to inspect the boiler.
- Have any control system part and any gas control that was under water replaced.
Boiler isolation valve must be power open, spring return
Viessmann · Boiler isolation valves
Boiler isolation valves must be power open with spring return. Viessmann sells them as accessories.
- Select a power open, spring return isolation valve.
- Match the valve size to the boiler model.
Boiler location and flue gas system
Viessmann · Vitodens 222-F, B2TB 68 and 125
The boiler is a direct vent appliance and can be installed for sealed combustion regardless of room size or ventilation. It can go in living areas, unventilated utility rooms, cupboards, closets, alcoves with no combustible clearance, and attics with a direct outlet for the flue. Use the Viessmann PPS concentric flue system for sealed combustion or side wall venting, certified with the boiler. Vertical venting is possible with AL29-4C single-wall room-air-dependent venting (UL listed Category IV). See the Venting System Installation Instructions for details.
Boiler location restrictions
Viessmann · Vitocrossal 200 CM2 186 to 620
Do not install the boiler where halogenated hydrocarbons can reach the combustion air, such as in barber shops, beauty salons, print shops, chemical cleaners or laboratories. Boiler efficiency depends on return water temperature and load.
- Check the installation room for halogenated hydrocarbons before installing.
- Keep the boiler room frost-free and properly ventilated.
Boiler number shown in multi-boiler systems
Viessmann · Vitotronic 200 (type H01B) in multi-boiler systems
In a multi-boiler system each Vitotronic 200 shows its boiler number on the standard display, next to the boiler water temperature.
Boiler pump may run continuously after reset
Viessmann · Vitodens 200-W B2HA 19, 28, 35
After a reset of the Vitodens 200 B2HA, coding address 30:0 can change to 30:3, which makes the boiler pump run continuously.
- Verify that coding address 30:0 is set.
- Adjust to 30:0 if necessary (see page 54).
Boiler pump runs continuously after switching to multi-boiler operation
Viessmann · Vitodens 200 B2HA in multi-boiler systems
In multi-boiler operation, coding address 30:0 can change to 30:3 on its own, which makes the boiler pump run continuously.
- Verify that coding address 30:0 is set on each boiler.
- Set 30:0 if necessary (see page 59).
Boiler pump runs continuously in multi-boiler setup
Viessmann · Vitodens 200-W B2HA 45, 60
When switched from single boiler to multi-boiler operation, coding address 30:0 may reset to 30:3, making the boiler pump run continuously.
- Verify coding address 30:0 on each boiler.
- Adjust to 30:0 if necessary (see page 54).
Boiler reporting 0 degrees is skipped
Viessmann · Default 8-boiler GW6B configuration
A boiler that reports 0 degrees boiler water temperature has all its other points skipped. This speeds up the refresh of the points for boilers that are present, because the gateway does not poll a boiler that is not there.
Boiler room location and air quality
Viessmann · All CM2 models
Halogenated hydrocarbons or aggressive chemicals in the combustion air can corrode the heat exchanger.
- Do not install the boiler where halogenated hydrocarbons are present in the combustion air, such as barber shops, beauty salons, printing shops or chemical cleaners.
- Keep chemicals such as bleach, hair spray, methyl chloride, carbon tetrachloride or perchloroethylene out of the boiler room.
- Keep the boiler room free of high dust or humidity levels.
Boiler room location and combustion air restrictions
Viessmann · Vitocrossal 300 CA3B Dual Fuel
Do not install the boiler where halogenated hydrocarbons are in the combustion air, such as in barber shops, beauty salons, print shops, chemical cleaners or laboratories. The boiler room must be frost-free and well ventilated.
- Check that the combustion air is free of halogenated hydrocarbons.
- Keep the boiler room frost-free and ventilated.
Boiler room location and flue gas temperatures
Viessmann · Vitocrossal 300 CA3B, all sizes 2.5 to 6.0
Do not install the boiler where halogenated hydrocarbons are present in the combustion air. Flue gas temperature varies with boiler water temperature.
- Keep the boiler room free of frost and properly ventilated.
- Avoid locations such as barber shops, beauty salons, print shops, chemical cleaners and laboratories.
- Flue gas temperature may range from 77°F (25°C) to 257°F (125°C) depending on boiler water temperature.
Boiler section count and lead/lag layout
Viessmann · Vitocrossal 300 CA3B Dual Fuel, 2.5 to 6.0 and multi-boiler systems
Models 2.5, 3.0, 3.5 and 4.0 have two boiler sections. Models 5.0 and 6.0 have three. In a single boiler, section A is the lead (section 1), B is lag 1 (section 2), and C is lag 2 on the 5.0 and 6.0 (section 3). In multi-boiler systems the first boiler's controls show all sections. A minimum of 4 and a maximum of 8 boiler sections are allowed.
- Confirm the number of boiler sections for the model.
- In a multi-boiler system, set up the lag control on the 2nd, 3rd or 4th boiler.
Boiler section status symbols
Viessmann · Vitocrossal 300 CA3B Dual Fuel programming unit and service display
The flame symbol shows the heat output of each boiler section. A solid white circle means the section is enabled and running, a solid grey circle means it is available but not called, and a crisscrossed circle means it is unavailable. The number under the circle shows current output.
- Flame with one line long: 1 to 33% output.
- Flame with half length: 34 to 66% output.
- Flame at full length: 66 to 100% output (67 to 100% on the service display).
- Solid white circle: enabled and operating.
- Solid grey circle: available, not called.
- Crisscrossed circle: unavailable.
Boiler sequence icons in the standard menu
Viessmann · Vitotronic 300-K (type MW2B) cascade
Solid white: boiler enabled by the cascade and operating. Solid grey: available but not enabled. Solid black and crossed out: not available for heat production.
Boiler serial number for parts orders
Viessmann · Vitodens 200-W B2HA 45, 60 parts ordering
Parts orders need the 16-digit boiler serial number from the bar code label, or the 12-digit ASME/NB serial. Both are under the front enclosure panel. Some parts are not reverse compatible with earlier B2HA versions.
- Remove the front enclosure panel to read the serial number.
- Quote the serial number on every parts order.
Boiler timeout after five minutes with no data
Viessmann · LON cascade communication
If a boiler sends no data for five minutes, the gateway treats it as offline and reports zero for all its points. The gateway skips that boiler until it reports a non-zero boiler water temperature. This applies to LON communication between boilers only, not KMK.
Boiler water temperature is set by the Vitocontrol-S
Viessmann · Vitocontrol-S with Vitotronic 100 GC1 boilers
In a multi-boiler system the Vitocontrol-S sets the boiler water temperature for every boiler control unit. This cannot be changed on the Vitotronic 100, GC1.
- Make the boiler water temperature change on the Vitocontrol-S, not on the Vitotronic 100.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.