Viessmann Boiler: Boiler piping with a chiller (heating/cooling)
Boiler piping with a chiller (heating/cooling) on a Viessmann boiler: When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler through valves so chilled medium cannot enter the boiler. Hot water coils in air handlers exposed to refrigerated air need flow control valves or another automatic means to stop gravity circulation during cooling.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix boiler piping with a chiller (heating/cooling): step by step
- Pipe the chilled medium in parallel with the boiler using valves.
- Add flow control valves or an automatic means on hot water coils in air handlers exposed to refrigerated air.
- Use a spring-loaded flow check valve and a safety header with automatic air vent and pressure relief valve as shown.
- Check the chiller manufacturer's installation instructions for additional requirements.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB installation instructions, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.