Viessmann Boiler: Balancing valve placement
Balancing valve placement on a Viessmann boiler: Valve position is needed for laminar flow through the boiler.
Applies to: Vitorond 200 VD2 boilers
How to fix balancing valve placement: step by step
- Install any balancing valve 5 pipe diameters from fittings.
- Install any balancing valve 10 pipe diameters from circulation pumps.
- Have a certified balancing firm balance the system before boiler start-up.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitorond 200, VD2 Series 320 to 1080 Technical Data Manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.