Viessmann Boiler: Autobinding reset without a power cycle
Autobinding reset without a power cycle on a Viessmann boiler: Use this when the LON participant number has to change without a power cycle, or when a tool binding must be cleared.
Applies to: Versatronik 503 rotary dial S1
How to fix autobinding reset without a power cycle: step by step
- Set the S1 dial to position 9.
- Wait 10 seconds.
- Press and hold the service button for 2 seconds.
- Wait 10 seconds.
- Set the dial to the desired boiler number.
- Wait about 10 seconds for the new address to take effect.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.