Viessmann Boiler: Application 7: zone control wizard, ZC1 weather compensated with ZC2 and ZC3 fixed setpoint
Application 7: zone control wizard, ZC1 weather compensated with ZC2 and ZC3 fixed setpoint on a Viessmann boiler: Three heating circuits: ZC1 gets a call from a Multizone Control and runs weather compensated, ZC2 gets a call from a second Multizone Control (two zone valves, fixed setpoint), ZC3 comes from a snow melt control and runs fixed setpoint with a pump on the 157 output. ZC1 has no pump in this layout.
Applies to: Application 7, ZC1 weather compensated with ZC2 fixed setpoint
How to fix application 7: zone control wizard, zc1 weather compensated with zc2 and zc3 fixed setpoint: step by step
- Select the number of zone circuit connections to match the controls wired to the DE connections, then press OK.
- For ZC1, arrow down to the weather compensated function and press OK.
- Adjust slope and shift to set the heating curve. The screen shows the curve moving as you change them.
- Press OK to continue. These settings can be changed later.
- For ZC2, select fixed setpoint, press OK, and set the zone target temperature.
- For ZC3, select fixed setpoint, set the zone target temperature, and select the 157 pump output.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
More commissioning tips for boiler
Source: Vitocrossal 300 CU3A application guide, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.