Viessmann Boiler: Adjusting the fixed high limit to 99 °C / 210 °F (VD2 only)
Adjusting the fixed high limit to 99 °C / 210 °F (VD2 only) on a Viessmann boiler: Applies to Vitorond 200 VD2 where the factory fixed high limit is 110 °C / 230 °F. Not required for CT3 or CM2.
Applies to: Vitorond 200 VD2
How to fix adjusting the fixed high limit to 99 °c / 210 °f (vd2 only): step by step
- Disconnect power to the control and burner.
- Unclip the fuse box and swing it upwards.
- Turn the slotted screw on the rear of the fixed high limit until the slot points to 99 °C / 210 °F.
- Refit the fuse box.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 100 GC1 installation and service instructions, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.