Viessmann Boiler: Adjust the differential pressure bypass valve

Updated · by Aurora Star Tech Inc.

Adjust the differential pressure bypass valve on a Viessmann boiler: The bypass valve keeps a minimum flow through the boiler when zone valves close and reduces noise. It is set by finding the tipping point and then backing off one turn.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotron 100 VLN2 hydronic piping

How to fix adjust the differential pressure bypass valve: step by step

  1. Turn the bypass valve clockwise until it stops.
  2. Turn on all heating zones and let them run a couple of minutes.
  3. Slowly turn the valve counterclockwise until a temperature rise is felt on the outlet side. This is the tipping point.
  4. Turn the valve one further full turn.
  5. Set the thermostats to their normal temperatures.
  6. Piping can get hot quickly when the valve opens, so open it slowly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4

More commissioning tips for boiler

Source: Vitotron 100 VLN2 installation and service instructions, p. 9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977